    Flexible coupling
    How do you slide flexible coupling on 3" pvc drain pipe?
    massplumber2008's Avatar
    massplumber2008 Posts: 12,832, Reputation: 1212
    Senior Plumbing Expert
     
    #2

    Feb 9, 2009, 03:09 PM
    Hi James:

    You don't slide a rubber sleeve on pvc pipe. Instead you fold the rubber sleeve back on itself (effectively folding the sleeve in half) and then slide the pipe into place and FLIP the rubber sleev forward to couple up to the pipe. Then you SLIDE the SS clamp over the rubber sleeve.

    Let me know if that makes sense...

    Mark
    Milo Dolezal's Avatar
    Milo Dolezal Posts: 7,192, Reputation: 523
    Plumbing Expert
     
    #3

    Feb 9, 2009, 09:40 PM

    However, if you are trying to use Flex Seal Coupling ( all rubber with 2 s.s. bands ) than you : cut the pipe, spray both ends with WD 40, slide coupling all the way on one side, bring in second piece of pipe and slide over the cut. Secure both bands. Make sure you are Half-n-Half over each end of pipe.

    If you are using Fernco couplings (No-Hub couplings / with metal sleeve ), do as Mark advices.
    james866's Avatar
    james866 Posts: 2, Reputation: 0
    New Member
     
    #4

    Feb 11, 2009, 05:48 PM

    Using the WD40 and tapering the ends of the thick coupling and pvc pipe helped keep it from hanging up while sliding on - still VERY tight.
    massplumber2008's Avatar
    massplumber2008 Posts: 12,832, Reputation: 1212
    Senior Plumbing Expert
     
    #5

    Feb 11, 2009, 07:15 PM
    Hey James...

    I disagree with you... ;)

    There are a number of different clamps/couplings (see pictures) to choose from. In fact, the coupling you have chosen is the wrong clamp for any above-ground application!! I hope you aren't planning on having this inspected because it would fail!

    Fernco couplings with rubber sleeve and SS bands (last pic.) are strictly intended for UNDERGROUND applications. These will not provide you with any strength especially if this is for a vertical stack application. They are sold everywhere as repair clamps, but are not code legal above-ground anywhere that I know of...

    The rest of these SHIELDED clamps are acceptable for above-ground applications...depending on pipe type. The shielded clamp is the difference here..adds stability/strength to application. Fernco clamps are simply rubber sleeves with clamps...not reasonable above ground for real plumbing.

    Good luck!

    MARK
    Attached Images
        

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Flexible coupling vs. No-hub coupling [ 3 Answers ]

I have to add a sanitary tee fitting to a PVC 3" vertical waste stack. I haven't cut into the pipe yet, but I'm reasonably certain that I'm not going to have enough slack or play in the either end of the pipe to work in a PVC fitting and cement it. From reading this forum it sounds like a no-hub...

Repair coupling and rigester coupling [ 4 Answers ]

What is the deffernce between the repair coupling and the rigester coupling in PVC fittings? I knew the deffrence in shape and that the first is used in small places wher you add or fix an exsisting line, and the last one is always used in first fixing and installatin. But can I always use the...

Azo coupling [ 1 Answers ]

Whydoes azo coupling at ortho position of 1-naphthol occur if para position is occupied? And why does diazonium coupling ortho position or para position of phenol?

Azo Coupling [ 1 Answers ]

Why does coupling of para-nitrobenzene diazonium chloride occur mainly para to the N(CH3)2 group of N,N-Dimethylaniline but ortho to -OH group of 2-naphthol?


View more questions Search