    Is a PVC coupling for DWV the same as a PVC coupling for water?
    Is a PVC Drain Waste and Vent (DWV) coupling the same as a coupling for PVC water pipe?
    KISS's Avatar
    KISS Posts: 12,510, Reputation: 839
    Uber Member
     
    #2

    Dec 25, 2009, 10:50 PM

    NOPE! See the dimensions linked on this page. Dimensions
    speedball1's Avatar
    speedball1 Posts: 29,301, Reputation: 1939
    Eternal Plumber
     
    #3

    Dec 26, 2009, 06:20 AM
    Quote Originally Posted by AaronT View Post
    Is a PVC Drain Waste and Vent (DWV) coupling the same as a coupling for PVC water pipe?
    No! While All PVC couplings , (see image) Work pretty much the same way. Pressure couplings are built to contain pressure while DWV coupling are not. Doe this answer your question? Tom
    AaronT's Avatar
    AaronT Posts: 2, Reputation: 1
    New Member
     
    #4

    Dec 27, 2009, 07:13 AM
    Yes, well most of it; I did not know if the couplings had a different depth of glue surface, along with the pressure rating, or if it was marked somehow on the fitting it self. I know that a coupling I've been using for DWV has a 1-1/2" glue surface for 4" PVC. I am in a place that is somewhat hard to get pipe I'm use to using for water which would be a belled end with a compression type seal, but I only have Sch 40 PVC pipe and will need a coupling. Any help on this is appreciative.
    speedball1's Avatar
    speedball1 Posts: 29,301, Reputation: 1939
    Eternal Plumber
     
    #5

    Dec 27, 2009, 09:37 AM
    Quote Originally Posted by ;
    . I am in a place that is somewhat hard to get pipe I'm use to using for water which would be a belled end with a compression type seal, but I only have Sch 40 PVC pipe and will need a coupling. Any help on this is appreciative.
    Drainage couplings are shorter with less glue surface. Pressure couplings have more glue surface to contain the pressure.
    If I were in a tight spot and had to couple two pipes together I'd use a dresser coupling, (see image) Good luck, Tom

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Fernco neoprene coupling to connect two PVC pipes instead of a pvc repair coupling? [ 3 Answers ]

Hi, A plumber was replacing some plumbing in our shower area. He connected two 2" PVC pipes that ran directly into each other with a Fernco Neoprene Coupling. In another place, he connected two 3" PVC pipes that ran directly into each other with a second Fernco Neoprene Coupling. In both cases...

Standard water Pipe compression coupling sizes [ 4 Answers ]

I recently removed my shower mixer valve which was faulty, the intention was to replace it with a new unit. When I checked the compression coupling sizes they were 22mm, this does not seem to be a standard size which from visits to the hardware stores seems to be 15mm. Does any one know of any...

Flexible coupling vs. No-hub coupling [ 3 Answers ]

I have to add a sanitary tee fitting to a PVC 3" vertical waste stack. I haven't cut into the pipe yet, but I'm reasonably certain that I'm not going to have enough slack or play in the either end of the pipe to work in a PVC fitting and cement it. From reading this forum it sounds like a no-hub...

Repair coupling and rigester coupling [ 4 Answers ]

What is the deffernce between the repair coupling and the rigester coupling in PVC fittings? I knew the deffrence in shape and that the first is used in small places wher you add or fix an exsisting line, and the last one is always used in first fixing and installatin. But can I always use the...

Joining Copper & PVC DWV [ 3 Answers ]

I am relocating my toilet (3 ft ). The current drain is 3" copper. How do I connect the PVC to the copper pipe?


View more questions Search