    Well pump
    Pressure slowly drops even with no water running. Checked for water leaks. None anywhere in system.
    jlisenbe's Avatar
    jlisenbe Posts: 5,020, Reputation: 157
    Uber Member
     
    #2

    May 28, 2012, 05:12 AM
    Probably a leaking checkvalve. Is your pump in the well or above ground?

    Might also be a leaking flapper valve in a toilet which allows the toilet the constantly draw water to keep the bowl full.
    speedball1's Avatar
    speedball1 Posts: 29,301, Reputation: 1939
    Eternal Plumber
     
    #3

    May 28, 2012, 06:05 AM
    Quote Originally Posted by gdoldbuoy View Post
    Pressure slowly drops even with no water running. Checked for water leaks. None anywhere in system.
    Well something's leaking in your system. Let's check and find out where. This can be done through the process of elimination. Shut the water off to the house and watch the gage. If it still drops the problem's on the pump side. If it holds steady then check the house for leaks.
    If the problem's on the pump side I'd be giving a hard look at the foot/check valve or the suction line and if it's in the house a flapper leak in the toilets or a break in the main or a branch. Good luck and let me know what you find. Tom
    jlisenbe's Avatar
    jlisenbe Posts: 5,020, Reputation: 157
    Uber Member
     
    #4

    May 28, 2012, 05:26 PM
    Very good advice.

    That's about it. What kind of pipe, plastic or galvanized? If galvanized, I am assuming there is a union you can undo?
    gdoldbuoy's Avatar
    gdoldbuoy Posts: 2, Reputation: 1
    New Member
     
    #5

    Jun 1, 2012, 03:39 AM
    Quote Originally Posted by speedball1 View Post
    Well something's leaking in your system. Let's check and find out where. This can be done through the process of elimination. Shut the water off to the house and watch the gage. If it still drops the problem's on the pump side. If it holds steady then check the house for leaks.
    If the problem's on the pump side I'd be giving a hard look at the foot/check valve or the suction line and if it's in the house a flapper leak in the toilets or a break in the main or a branch. Good luck and let me know what you find. Tom
    Pump side. Could hear water running through what appeared to be check valve (flomatic). Valve is located on pump side of gauge and switch from the tank. Pump is submersable type.

    Quote Originally Posted by gdoldbuoy View Post
    Pump side. Could hear water running through what appeared to be check valve (flomatic). Valve is located on pump side of gauge and switch from the tank. Pump is submersable type.
    Anything special about changing valve besides turning off pump power and closing tank valve?

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Pump lost prime and overheated motor runs but does not pump is the pump fried [ 4 Answers ]

Over night the pump lost primed and melted the sched. 40 fittings I replaced all the fittings and cannot get pump to prime the motor runs is it possible that the propeller was damaged from the heat?//

How to calculat for Diaphragm tank V for a booster pump station include a Jocky pump? [ 0 Answers ]

How to calculate the Diaphragm tank "V" for a booster pump station include a 4 duty pumps and Jockey pump "Q 1p" each pump = 40 L/s. "Qj" Jockey Pump = 10.5 L/s. Can calcaulate based on each Q ? ("Q1p" , "Q4p" or "Qj")

Does a condenser centrifugal pump suit t work asa chilled water pump [ 0 Answers ]

I have 3 cenreifugal pump which are used for the condenser cooling water recirculation, may I could use it as a chilled water pumps and get another smaller pumps for cooling water recirculation, thank u in advance.

Is Meyers pentair sewage ejector pump model SR1830 a quality pump? [ 1 Answers ]

Just installed a sewage ejector pump and I'm somewhat concerned about the manufacture. Not seeing very much information about Meyer. I see Zoeller and Little Giant, so I'm wondering if I got a quality systems. Considering all that was required to get the system in I don't want to revisit this for...


View more questions Search