    Distance from Adjacent Shower Door for Forced Air Heater
    I am installing a King Brand PAW model 240 volt forced air heater in my bathroom. King manual only requires 6inch from adjacent wall. See attached link-
    http://www.king-electric.com/prodtemp.asp?prodID=HEAT_PAW_DEC_SL_INFO
    I am installing on dedicated 20amp 240 volt dedicated circuit with switch on other side of shower.
    Does NEC say anything regarding heater distance from shower door?
    Thanks.
    tkrussell's Avatar
    tkrussell Posts: 9,659, Reputation: 725
    Uber Member
     
    #2

    Dec 16, 2011, 03:32 AM
    No, just follow manufacturers instructions and common sense.
    donf's Avatar
    donf Posts: 5,679, Reputation: 582
    Printers & Electronics Expert
     
    #3

    Dec 16, 2011, 08:01 AM
    Location of the switch is paramount. You do not want someone who is in the shower to be able to reach and operate the switch while in the shower.

    This could lead to a fatal shock to the person in the shower.
    sls_medford's Avatar
    sls_medford Posts: 4, Reputation: 1
    New Member
     
    #4

    Dec 18, 2011, 11:27 PM
    I know what is safe- but want to know if NEC comments anywhere regarding appliance distance from shower, heater locations in bathroom?
    tkrussell's Avatar
    tkrussell Posts: 9,659, Reputation: 725
    Uber Member
     
    #5

    Dec 19, 2011, 08:17 AM
    I answered this question, No, there is no NEC requirements just follow manufacturers instructions.
    stanfortyman's Avatar
    stanfortyman Posts: 5,598, Reputation: 279
    Electrical & Lighting Expert
     
    #6

    Dec 19, 2011, 08:25 PM
    Quote Originally Posted by donf View Post
    Location of the switch is paramount. You do not want someone who is in the shower to be able to reach and operate the switch while in the shower.

    This could lead to a fatal shock to the person in the shower.
    According to the NEC the switch can still be directly adjacent to the shower. Do you think this would have stayed in the code if there were any safety issues?

    Can you explain how this fatal shock will occur if the switch is wires and installed properly?
    sls_medford's Avatar
    sls_medford Posts: 4, Reputation: 1
    New Member
     
    #7

    Dec 20, 2011, 10:17 PM
    Thanks! I will have my rough-in inspection from local government- let you know the results later.
    sls_medford's Avatar
    sls_medford Posts: 4, Reputation: 1
    New Member
     
    #8

    Jan 10, 2012, 10:39 PM
    Got my rough-in inspection! No questions at all regarding the heater! Thanks for your help.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Heater gas forced air [ 1 Answers ]

I have a combo heat and cooling system the problem is with the heat the unit cycles glow light comes on the furnace firers up and then shuts down I have to reset the system two maybe three times what causes this seem like every night I have to go through this what can it be

Forced Hot Air Heater [ 1 Answers ]

I've noticed lately that my forced hot hair heating system is louder than it used to be. I have to turn up the TV when it goes on. I don't recall it ever being that noticeable or loud. Any suggestions on what it could be?

Forced air heater no heat [ 1 Answers ]

I have an old Day and Night (over 16 y/o) gas forced air heater that is blowing cool air only. The Model # is 8OU-19A or 8QU-19A. The igniter/pilot appears to be working fine & when the temp controls are raised the fan comes on but the main burners do not. Where do I start, even if the pilot seems...

Day & Night forced air heater keeps blowing cold air [ 1 Answers ]

Yesterday my heater was working as normal. Today I replaced the filter in my Day & Night forced air heater. Later I bumped my thermostat when walking by it, but I'm not certain that this caused the problem. My heater turned on and blew hot air. I turned it all the way down, but the fan...

Forced air heater [ 1 Answers ]

Blows 3 amp fuse. After fuse blows fan comes on. Ignitor works prior to fuse blowing but no gas. One resistor on board appears to have black mark.


View more questions Search