    photodog01's Avatar
    photodog01 Posts: 2, Reputation: 1
    New Member
     
    #1

    Jan 15, 2009, 09:37 PM
    Replacing cast iron pipe w/PVC
    I read some of the other posts regarding CI to PVC. I get the general idea. What is the correct connector for this situation?

    Greetings. I am in the midst of a bathroom remodel. I have removed the old, rusted, deteriorated cast iron pipe. The old pipe was a 3" which lead to a 3" cast iron pipe fitted into a 4" PVC pipe that drains out to the city sewer. I want to put 4" PVC back in the bathroom toilet drain. My problem, is that the cast iron pipe that the toilet drained into, also has the rest of the house draining into it also. The upper portion of the iron pipe reminds me of an octopus, with leads into a central area of the pipe.
    So, I have a 3" iron pipe that is tied into a 4" PVC that leads to the sewer system. The plumbing vent pipe is within reach so that I can attach the PVC and still have the metal pipe extend upwards through the walls and roof.

    Any and all assistance is appreciated.

    PD01

    If need be, I can upload a photo.
    Milo Dolezal's Avatar
    Milo Dolezal Posts: 7,192, Reputation: 523
    Plumbing Expert
     
    #2

    Jan 15, 2009, 09:42 PM

    Please, post photo. Thanks

    But in the interim: Fernco connectors can be used in your situation. They sell them to fit any size and type of pipe. Home Depot carries the basic ones; you will probably have to go to more professional store to get the other sizes.
    photodog01's Avatar
    photodog01 Posts: 2, Reputation: 1
    New Member
     
    #3

    Jan 17, 2009, 07:30 AM
    Quote Originally Posted by Milo Dolezal View Post
    Please, post photo. Thanks

    But in the interim: Fernco connectors can be used in your situation. They sell them to fit any size and type of pipe. Home Depot carries the basic ones; you will probably have to go to more professional store to get the other sizes.
    Here are a couple pic's that show the junction I am described.

    Name:  IMG_0907.jpg
Views: 3520
Size:  72.0 KB

    Name:  IMG_0909.jpg
Views: 8436
Size:  71.4 KB

    Name:  IMG_0911.jpg
Views: 19222
Size:  69.5 KB
    Milo Dolezal's Avatar
    Milo Dolezal Posts: 7,192, Reputation: 523
    Plumbing Expert
     
    #4

    Jan 17, 2009, 08:38 AM

    Thanks for the visual...

    Cut out the Multi-Y fitting. Remove the vertical pipe from where it connects to the 4" PVC . Also cut it below the ceiling. Leave yourself enough space so you can reconnect new pipe to it. You will be using 4"Cast Iron to 4" PVC Fernco fitting.

    Now, if I understand correctly, you want to upgrade toilet line to 4", get rid of the Multy-Y fitting and rest of the Cast Iron vertical drop. Run new horizontal toilet drain in 4" PVC below the ceiling. When you get to horizontal to vertical drop (where the Multy-Y used to be), use 4" Double Y fitting. One side will connect to your toilet with using street 45 fitting.

    The other side of the Y will connect the two 2" PVC drains. But first, you have to Combine those two into one pipe, about a foot before they reach the new 4" double Y. You combine them by using 2" Y and 2" street 45 fittings. Once combined, you will continue with on pipe towards your new 4" Double Y. There, glue in 4" x 2" reducing bushing into the other inlet of 4" Double Y, glue in short piece of 2" pipe pointing upwards, then 2"-45 fitting that will get you from vertical to horizontal - and connect the 2" horizontal run to it.

    I think that the 1 1/2" galvanized drain on the left is capped off. If so, disregard it. If it is active drain, than glue another 4"x 1 1/2" Y immediately bellow the new 4" double Y, pointing towards the concrete wall. Glue in 1 1/2" - 45 and connect.

    Install 4" Clean Out on vertical run, before the new 4" pipe turns from vertical to horizontal.

    You will have to support the new pipes. You could run the vertical pipe closer to the wall and attach it there. If it is active area, you should also protect the vertical drop from being damaged. In this case, you can run two 2"x 6", one from each side, floor to ceiling.

    (note: the drawing should read 4" toilet instead of 3" toilet )
    Attached Images
     

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Cutting through cast iron How is it possible to cut through a cast iron soil pipe [ 6 Answers ]

Cutting through cast iron How is it possible to cut through a cast iron soil pipe

Replacing cast iron drain pipe? [ 6 Answers ]

Put in a dishwasher and was working on the drain when I noticed the 2" cast iron drain pipe wasnt in very good shape. I spliced it with a sawzall ans the put pvc in and tried to use a boot on each end but it still leaks. Then from the cutting another joint in it started to leak. Ive decided its...

Replacing Cast Iron Tee with PVC [ 20 Answers ]

Hi: I was attempting to clean out a clogged drain at the sanitary tee and the cast iron at the plug broke. The cast iron sanitary tee is still in good shape. As I see it, I have 2 options: 1) Remove the broken piece of cast iron pipe that comes out of the sanitary tee and plug it with an...

Replacing old Cast Iron Sewer with PVC [ 1 Answers ]

I am remodeling a 2 bedroom house myself which sit on a crawl space and unfortunately I have to replace all plumbing and sewer systems inside the house. I was wondering what the best and easiest way to replace the cast iron sewer system with PVC. Do I need to replace the entire cast iron stack, how...

Replacing cast iron pipes [ 3 Answers ]

I have an older home with cast iron pipes. I have to replace them due to stress cracks? How is this done and should I replace the cast iron with PVC?:confused:


View more questions Search