    I know it used to be just bedrooms, but has that changed with the 2008 code? Also, I remember that I use to have to run individual circuits to each bedroom, each with its own neutral. Is that still the case or have they come out with something new that allows two AFCI circuits to use the same neutral? :confused:
    stanfortyman's Avatar
    stanfortyman Posts: 5,598, Reputation: 279
    Electrical & Lighting Expert
     
    #2

    Mar 12, 2008, 01:46 PM
    There are some two-pole AFCIs. I know Cutler makes them in their BR series.

    Where are they required? What code cycle do you follow??

    Just because there is a new NEC cycle does NOT mean every place adopts it in it's entirety. Even those that do adopt it often have amendments.
    lbartowski's Avatar
    lbartowski Posts: 5, Reputation: 1
    New Member
     
    #3

    Mar 12, 2008, 02:11 PM
    Code Cycle?? I assumed that everyone on this forum followed the 2008 NEC code that went into effect January, 08... what planet do you do electrical work on? :)
    stanfortyman's Avatar
    stanfortyman Posts: 5,598, Reputation: 279
    Electrical & Lighting Expert
     
    #4

    Mar 12, 2008, 04:01 PM
    Obviously not the same one as you. :p

    Yes, code cycle. Why would you assume this.

    I guess you don't get around. EVERY place is different. Some places are still under the 1999 NEC.
    NY follows two different electric codes. As of 1/1/08 it follows it's resi code which is based on the 2002, and for commercial it is now under the 2005 NEC.
    Stratmando's Avatar
    Stratmando Posts: 11,188, Reputation: 508
    Uber Member
     
    #5

    Mar 12, 2008, 04:38 PM
    Bedrooms, last I knew.
    stanfortyman's Avatar
    stanfortyman Posts: 5,598, Reputation: 279
    Electrical & Lighting Expert
     
    #6

    Mar 12, 2008, 06:20 PM
    Quote Originally Posted by Stratmando
    Bedrooms, last I knew.
    1999 NEC - Bedroom receptacles
    2002 NEC - ALL bedroom outlets; including receptacles, lighting and smoke detectors
    2005 NEC - Same as 2002
    2008 NEC - MOST branch circuits supplying outlets (receptacle, lighting, smokes, etc) in MOST habitable rooms of the house. Rooms like the kitchen, garage, etc, are exempt.



    WHAT CODE CYCLE ARE YOU UNDER?

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Suggestions required [ 1 Answers ]

I would like Suggestions from all of you who reading it. Please advise me best suggestions. Here is my story>>I am from Pakistan. My girl is living in usa. We want to marry . She has British passport. She has green card in usa. We want to live in uk after marriage. Can any one tell me Is it...

Payment Required [ 2 Answers ]

You need $28,974 at the end of 10 years, and your only investment outlet is an 8 percent long-term certificate of deposit (compounded annually). With the certificate of deposit, you make an initial investment at the beginning of the first year. 1. What single payment could be made at the...

GFCIs required? [ 2 Answers ]

I am wiring a 40' x 68' barn/shop, rated as residential with a 200 amp service. It is being used to store a couple of boats and trailers in the winter, with a shop to work in. Do all the receptacles in the building need to be GFCI protected? Thank you, Guy

Information required [ 4 Answers ]

My question is " How to know if a woman is aroused?" Or is she just faking it??

When is a permit required? [ 5 Answers ]

I'm located in Montgomery County, MD and am going to be doing some work in the basement. When is a permit required when working on plumbing? I plan on moving the shower drain and vent about a foot, and the toilet drain and vent about 4 inches. Do I even need a permit?


View more questions Search