    S-trap Transition from brass to PVC
    Hello

    I have an older home. The previous owners replaced a wall hung sink (in a 40's style art deco bathroom) with a silly short vanity. I'd like to return it to it's former glory with a wall hung sink. The waste line is PVC, and goes through the floor into the basement (the entire cast iron waste line has been replaced with PVC.

    What I have now is a 1 1/4 " PVC S-trap with a transition coupling to 1 1/2" PVC above the floor. I am unsure of where I should transition from brass to PVC. Do I run the brass 1 1/4" line entirely through the floor and then cut a segment of PVC out before it enters the main line, and use a coupling that increases to 1/1/2 inch there? Or do I have to maintain the 1 1/2" coupling above the floor with the coupling showing?

    Thanks for any help
    Karl
    speedball1's Avatar
    speedball1 Posts: 29,301, Reputation: 1939
    Eternal Plumber
     
    #2

    Feb 23, 2008, 05:44 AM
    What I have now is a 1 1/4 " PVC S-trap with a transition coupling to 1 1/2" PVC above the floor. I am unsure of where I should transition from brass to PVC. Do I run the brass 1 1/4" line entirely through the floor and then cut a segment of PVC out before it enters the main line, and use a coupling that increases to 1/1/2 inch there? Or do I have to maintain the 1 1/2" coupling above the floor with the coupling showing?
    Of course you realize that "S" traps are outlawed in the US and Canada.
    Having said that I'll answer your question. This is simply a question of what will look the best and in my opinion extending the metal tailpiece below the floor line and covered with a escutcheon plate will give you a cleaner, neater looking installation. Good luck, Tom
    Karl D's Avatar
    Karl D Posts: 5, Reputation: 1
    New Member
     
    #3

    Feb 23, 2008, 07:31 AM
    Thank you for the response

    -- No, I did not know that s-traps are illegal, it makes me wonder why I even bothered with a home inspection prior to buying the place. It would be painfully obvious to anybody who saw it that the "goings on" under the bathroom sink was not original to the house, and no more than a few months old. Will this give me problems then (The s-trap works fine now).. Is it necessary to solder a (? Male or female) to the brass, and then screw it into the PVC or can I just line them up and use the coupling?. thank you!
    speedball1's Avatar
    speedball1 Posts: 29,301, Reputation: 1939
    Eternal Plumber
     
    #4

    Feb 23, 2008, 11:26 AM
    By "coupling" I hope you mean a compression fitting,(see image). You will take and prime and glue a 1 1/2" PVC compression fitting on to the 1 1/2" PVC pipe under the floor line. You will place a 1 1/2" X 1 1/4" Nylon washer in the compression fitting to convert from 1 1/2 to 1 1/4". That's all there is to it. Good luck, Tom

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Copper vs. PVC vs. Brass vs. Rubber [ 4 Answers ]

Hey all... new to the boards. Wanted to ask about using copper pipe for the inlet & outlet piping of the pump. How is it affected by the Cl levels? I work for a company where I can get FREE 1.5" Cu and ALL fittings... I wanted to make my system look better by doing it all in cooper and...

Connecting brass drain of a tub to pvc waste line [ 1 Answers ]

Hi, I am plumbing a new american standard tub. The overflow/waste drain is attached and in place. My existing waste line is 1 1/2" pvc, but the brass drain seems to be someplace between 1 1/4" and 1 1/2". What is the best method to attach to the wast line (with a p-trap before the...

PVC P-trap leaking [ 4 Answers ]

I have just installed vessel lavatories in new bathroom. There is no problem with draining, but despite tightening I have leaks from the trap compression nuts and where the tailpiece goes into the extension. Water seems to flow down while faucet is running but shortly thereafter, it appears at...

Where to buy oatey abs/pvc transition cement (green)? [ 1 Answers ]

Does anyone know if any of the big box stores or another national chain carry the oatey abs/pvc green transition cement? Thanks

P-trap GAP - p-trap too low to meet sink drain extension [ 13 Answers ]

I just took an old crane drexel sink off the wall and replaced it for the time being ( I want to fix the older sink) with a cheap vanity/sink set. All that was easy enough, but now to my chagrin I can't finish the job. The p trap is too low, the extension pipe from the sink doesn't go all...


View more questions Search