    No heat to second floor bedroom
    I live in a colonial style house with 3 bedrooms on the second floor. Cool air flows through the registers in the master bedroom while the heat supply to the other 2 smaller bedrooms seems OK, though could be better. I have closed some of the registers on the first floor but this has not rectified the problem. Any suggestions about what to do next? Thanks.
    hvac1000's Avatar
    hvac1000 Posts: 14,540, Reputation: 435
    Heating & Air Conditioning Expert
     
    #2

    Nov 14, 2007, 02:30 PM
    You need to find the restriction in the line going to the upstairs. Is this a heat pump system? Is your furnace filter clean? How much force is behind the air movement?
    cornrice's Avatar
    cornrice Posts: 3, Reputation: 1
    New Member
     
    #3

    Nov 14, 2007, 04:05 PM
    Thanks for the quick reply. I have a gas furnace that is only 4 yrs old and the filter was recently changed. The force of the air is moderate in the bedrooms, stronger on the first floor. Where would I find the restriction in the line going upstairs? Don't know a lot about heating systems.
    hvac1000's Avatar
    hvac1000 Posts: 14,540, Reputation: 435
    Heating & Air Conditioning Expert
     
    #4

    Nov 14, 2007, 04:39 PM
    You could look for a damper handle on the supply to the upstairs. You might also check into a higher blower motor speed.

    You might need to have a HVAC company out to take a look at your system also.
    cornrice's Avatar
    cornrice Posts: 3, Reputation: 1
    New Member
     
    #5

    Nov 14, 2007, 04:51 PM
    Ok, will do. Thanks so much for your help.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Not getting much heat to 2nd floor of the house [ 1 Answers ]

I am not getting much heat to the 2nd floor of our house. When the furnace is running there is very little air flow coming from the vents.

Heat doesn't reach top floor [ 7 Answers ]

Our heating and AC doesn't reach our top floor. We have a basement, first floor and second floor. During the summer we use window AC, but in the winter it gets incredibly cold up there. At one point it was 40F. We put in a fan to pull up the air, but that hasn't helped. We want to fix it...

No heat on First Floor [ 7 Answers ]

We have hot water baseboard, 1 circulator, 2 zone valves, 2 thermostats (1st flr, 2nd flr), Honeywell. Last week 1st flr heat stopped working. Forecasted to be cold in a couple of days, need to fix this. I think it's the powerhead on the 1st floor zone valve but need to make sure before I buy one. ...

Nuheat Electric Floor Heat [ 2 Answers ]

Hello, I am installing a Nuheat (Nuheat.com) electric floor heating pad. There are 2 wires from the pad that need to run up the wall and into a switch box. The switch box will have power coming in which connects to the thermostat and the thermostat connects to the heating pad. Does the wires...

No heat in bedroom baseboards [ 1 Answers ]

I installed a new Peerless hot water boiler. Have a single zone system which now provides plenty of heat to lower half of house, the upstairs bedrooms of this split level house has no heat. I installed a bleeder valve in one of the bedroom base boards and bled the system there until water started...


View more questions Search