    zeustogo's Avatar
    zeustogo Posts: 14, Reputation: 1
    New Member
     
    #1

    Oct 21, 2013, 04:31 AM
    Rheem heat pump reset button
    Just moved in and have a Rheem Heat Pump. In heat mode the fan runs constantly and after a little while the reset button on the condenser trips. I reset the condenser unit by pushing the red reset button and after a while it trips again. I suspect a dirty inside coil check it. It is very dirty where you can't get to it. Slide coil out and clean it from underneath. Very difficult. Finished start it up and it runs through it cycle a couple times and I go to bed. Wake up the condenser has tripped again. Plan to check pressures after work. Didn't check them earlier because of the dirty coil whick will skew the pressure readings. I work on air conditioners don't know much about heat pumps in heat mode. Anyone have suggestions to what is tripping the reset button on the condensing unit. It is a split unit and the condenser fans and compressor run after it is reset. I don't know the history on the unit. I get heating from 70 degrees in to 94 degrees out with the heat pump while it is working.
    zeustogo's Avatar
    zeustogo Posts: 14, Reputation: 1
    New Member
     
    #2

    Oct 21, 2013, 01:01 PM
    Checked pressure in heating mode. High side went to 450psi it pegged the low pressure. Put high pressure gauge on low side and pressure built up to 400psi and then I shut it off. Switched to air conditioning. Ambient temperature around 60 degrees, High side around 150 psi dropping and low side around 75 psi and dropping. I think the reversing valve is screwing up. Does anyone agree or does anyone have any other ideas?

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Where is the reset button on trane heat pump? [ 3 Answers ]

I changed the thermostat, it didn't work. Called tech support, they told me to reset my heat pump. I don't know how.

Rheem unit reset button keeps switching off? [ 0 Answers ]

Rheem hot water unit, reset button keeps switching off

Where is the reset button on a Rheem hot water tank [ 2 Answers ]

Where is the reset button on a Rheem hot water tank model number 71-305?

Rheem heat pump needs to be reset all the time why? [ 0 Answers ]

My rheem heat pump blows cold air,I have thermostat set at 70, 35 outside, but when I go outside I notice the fan is not working. Once I hit reset it works again for awhile.blows heat fine. What could be wrong? This has happened on more than one occasion.

Where is the reset button on a rheem heat pump, PPL-JAZ Model Series 14 SEER? [ 1 Answers ]

I have Rheem Heat Pump and it's not working. The fan is blowing, but no cold air. I can't find the reset button on it. It's a PPL-JAZ Model Series 14 SEER, and it was put in just over two years ago. I have looked at installation instructions, but I can't find the reset button. Can anyone help...


View more questions Search