    Service
    Ok got a question, I installed a service meter/combo Midwest trailer. Anyhow I was going take 20amps off it to power the septic pump since the panel accepts four breakers well the inspector rip me a new one and said I couldn't do it that way everything has to be feed from inside. Is he right? I tried looking it up in 2008 but couldn't find anything. I didn't see a problem doing it that way. What's your thoughts
    Mrgoat13's Avatar
    Mrgoat13 Posts: 5, Reputation: 1
    New Member
     
    #2

    Oct 6, 2013, 08:56 PM
    Here's a pics of what I'm talking about

    Meter Sockets - Breakers, Distribution & Load Centers - Electrical at The Home Depot
    stanfortyman's Avatar
    stanfortyman Posts: 5,598, Reputation: 279
    Electrical & Lighting Expert
     
    #3

    Oct 7, 2013, 04:00 AM
    He is totally wrong. That is exactly what those breaker spaces are there for.

    Obviously he did not cite a code for failing this, right?
    Ask him what section of the code it violated. If he says anything even remotely like "I just don't like it", or "I'd rather see...", then he is over stepping his authority.
    ma0641's Avatar
    ma0641 Posts: 15,675, Reputation: 1012
    Uber Member
     
    #4

    Oct 7, 2013, 06:22 AM
    I run 2 breakers off mine, outlets and a run to the garden house.
    Mrgoat13's Avatar
    Mrgoat13 Posts: 5, Reputation: 1
    New Member
     
    #5

    Oct 7, 2013, 11:25 AM
    No he didn't say any codes he just kept say its for services only. I didn't think I did anything wrong but boy was he mad about it
    QUOTE=stanfortyman;3564706]He is

    Totally wrong. That is exactly what those breaker spaces are there for.

    Obviously he did not cite a code for failing this, right?
    Ask him what section of the code it violated. If he says anything even remotely like "I just don't like it", or "I'd rather see...", then he is over stepping his authority.[/QUOTE]
    stanfortyman's Avatar
    stanfortyman Posts: 5,598, Reputation: 279
    Electrical & Lighting Expert
     
    #6

    Oct 7, 2013, 11:50 AM
    I didn't think I did anything wrong but boy was he mad about it
    Mad? Seriously?

    The guy has no clue then.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Installing new service entrance mast, service bypass meter & disconnect [ 4 Answers ]

Q. - Is the 2" rigid pipe (mast riser) with a threaded male pipe end attached to a bypass meter socket in a 2" meter socket hub (female pipe thread) a weather tight connection?

I want to start a tiffin service or packaged food service in punjab mkt [ 2 Answers ]

For tiffin or packaged food service What should be My target population is 350 tiffins 1) capital investment 2) manpower requirement 3) location and space availbility 4) marketing statergy 5) implementation process

How to wire for a 100 amp service to a garage from a 200amp service location [ 1 Answers ]

I have a 400 amp service that is attach to my house and I going to be putting in a garage about 200 hundred feet away from the main service panel, I would like to know what size wire to use for that length.


View more questions Search