    Pump won't prime
    We have a 2-stage (2 pipes coming out) above ground Water Ace Pump with a GE 1/2hp motor (4 bolts) has 2 set screws on either side. Anyway, it will not prime - when priming water does not run back down the pipe -- when motor is turned on it won't prime and there is large mix of air.

    The motor is relatively new and it has a new foot valve - was wondering if it could possibly be the impeller? Have dumped at least 60 gallons of water trying to get it to prime. Help!
    speedball1's Avatar
    speedball1 Posts: 29,301, Reputation: 1939
    Eternal Plumber
     
    #2

    Nov 29, 2012, 06:51 AM
    when priming water does not run back down the pipe
    I see what your saying but just to be sure When you pour in the water will it hold prime or does the water just run away? Let me know. Tom
    kar1976's Avatar
    kar1976 Posts: 2, Reputation: 1
    New Member
     
    #3

    Nov 29, 2012, 09:57 AM
    Water just runs away, will not hold prime
    jlisenbe's Avatar
    jlisenbe Posts: 5,020, Reputation: 157
    Uber Member
     
    #4

    Nov 29, 2012, 04:01 PM
    Anyway, it will not prime - when priming water does not run back down the pipe --
    Is it possible there is a check valve between the pump and the wellhead? If so, then water will run only from the impeller cage to the CV and no further. Jet pumps frequently have a port right at the wellhead where water can be poured directly into the wellpipe.
    speedball1's Avatar
    speedball1 Posts: 29,301, Reputation: 1939
    Eternal Plumber
     
    #5

    Nov 29, 2012, 04:12 PM
    You may have a new foot valve installed but it sure sounds like it failed in the open position, Rather then pull the well point why not install an check valve on the suction line ahead of the pump. Good luck, Tom

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Pump lost prime and overheated motor runs but does not pump is the pump fried [ 4 Answers ]

Over night the pump lost primed and melted the sched. 40 fittings I replaced all the fittings and cannot get pump to prime the motor runs is it possible that the propeller was damaged from the heat?//

How to prime the pump for a well that serves a geothermac heat pump [ 0 Answers ]

The power went off for a while this afternoon. When it came back on... the pump had lost it's prime... how do I prime the work to get my air conditioning on again?

Water well pump won't prime I know but I can't get to prime [ 0 Answers ]

I know how to prime a water well pump but Icant get it to prime . How would I know if something wrong with the pump


View more questions Search