    Ejector Pump Problems
    We have a new overhead sewer system with a ejector pump and when we run water, specifically our toilet as far as I know, in our basement we hear the water/pump by our ejector pump running loudly. When we looked we noticed that we had water by the ejector piping and pit, any thoughts?
    massplumber2008's Avatar
    massplumber2008 Posts: 12,832, Reputation: 1212
    Senior Plumbing Expert
     
    #2

    Aug 1, 2010, 06:27 PM

    Hi Swlstuds...

    MY first thought was that this is a new installation and it is possible that the pump is working fine but perhaps the CHECK VALVE was put in backwards or upside down... maybe?

    You say the pump runs, but you also see water around the pit... right? If so, this means, at the least, that the seals on the ejector system have failed and will need to be replaced. Do not take this lightly as these seals keep the sewer gasses/smells associated with these systems to a minimum.

    At a maximum, the check valve is backward (as mentioned), the impeller is clogged with debris...that kind of stuff.

    Who installed this and are they planning to pop by and inspect the issue? Sounds like they should.

    Let me know more...

    Mark
    JOANB's Avatar
    JOANB Posts: 1, Reputation: 1
    New Member
     
    #3

    Nov 18, 2012, 09:49 AM
    Our ejector pump in the basement hasn't been used in two years. It was working
    Fine last time, but I'm afraid to run water into it now. What should I do before
    Using it?
    massplumber2008's Avatar
    massplumber2008 Posts: 12,832, Reputation: 1212
    Senior Plumbing Expert
     
    #4

    Nov 19, 2012, 06:32 AM
    Run clean water into the tub and stand by the ejector pit for a few checking back and forth between the tub and ejector pit. If water pumps up and out you should be fine. If water starts to overflow the tank gaskets or the tub backs up then you will need to open the ejector pit and examine the pump... could be seized or hung up.

    Be sure to check that the dedicated electrical breaker is on and the pump system is plugged in properly!

    Mark

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Ejector pump [ 1 Answers ]

We have been in our "newly" built house for almost 7 years. The first ejector pump stopped working within the first year. It was replaced. Today the alarm is going off. The watchdog is saying that the pump isn't working.

Is Meyers pentair sewage ejector pump model SR1830 a quality pump? [ 1 Answers ]

Just installed a sewage ejector pump and I'm somewhat concerned about the manufacture. Not seeing very much information about Meyer. I see Zoeller and Little Giant, so I'm wondering if I got a quality systems. Considering all that was required to get the system in I don't want to revisit this for...

Sewage pump/ejector pump [ 2 Answers ]

My sewage/ejector pump sometimes won't shut itself off. It has gradually gotten worse as time goes by. What could be causing this? Any suggestions appreciated.

Ejector Pump [ 8 Answers ]

Just bought a new house with an unfinished basement. It has an ejector pump that is in an enclosed pit. The only incoming drains is from the clothes washer. I don't understand why the pump activates when I haven't used the washer for a couple of days. Could there be a leak in the check valve...


View more questions Search