    Bathroom exhaust fan near gas water heater
    I want to install a bathroom exhaust in a downstairs bathroom. The problem is that there is also the furnace and gas water heater in this room. They are not enclosed in any way. The room is around 100 sq/ft and is able to get plenty of fresh air from the rest of the basement, through the floor joists (no ceiling installed). Will I have a problem with the bathroom exhaust sucking out carbon monoxide from the hot water heater and/or the furnace? The exhaust fan would be roughly five feet away from the water heater and furnace.

    Thank you for your help.
    argaiu1017's Avatar
    argaiu1017 Posts: 92, Reputation: 8
    Junior Member
     
    #2

    Apr 13, 2011, 09:21 PM
    It is illegal to install a gas fired water heaters in bathrooms if u didn't know. If so u would have to use a sealed combustion water heater due to products of combustion, carbon monoxide, flue gases, etc. Or u must meet the 50 cubic ft per 1000btu input for proper and efficient operation of water heater.
    If anything its good.
    joypulv's Avatar
    joypulv Posts: 21,591, Reputation: 2941
    current pert
     
    #3

    Apr 14, 2011, 01:39 AM
    Comment on Clyeds's post
    Please stop copying barely relevant information from other sites into all your answers.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Bathroom exhaust near gas water heater [ 0 Answers ]

I want to install a bathroom exhaust in a downstairs bathroom. The problem is that there is also the furnace and gas water heater in this room. They are not enclosed in any way. The room is around 100 sq/ft and is able to get plenty of fresh air from the rest of the basement, through the floor...

How do I jump start an exhaust fan on a state select gas hot water heater? [ 1 Answers ]

It has happened before and a repair person jumped it and ordered a thermacoupler but it has lasted a year. I want to try it again myself to see if I can avoid a bill. The pilot light is lit.

York guardian gas furnace water in exhaust fan [ 0 Answers ]

I have an 80,000 Guardian Gas furnace. The rollout switch tripped the other day and it sounds like there is water in the Exhaust blower. First I wondered where the water might come from and if that tripped the rollout switch. Also where is the reset for the rollout switch ? I have a model...

Water Heater Exhaust Fan Running Continuously [ 0 Answers ]

I have a problem with my Kenmore power vent gas water heater: 40 Gal. Power Miser 8 and the model number is 409.737945. The problem is that the exhaust fan has been running continuously for two days, even the gas burner is off. I have checked the air pressure switch it seems okay. What else...

Exhaust Fan Constantly Blowing on Propane Water Heater [ 1 Answers ]

Hello, I have noticed that the exhaust fan constantly blows on my State Select Propane Water Heater. Is this normal, or should it only come on when the water heater is actually heating? Thanks,


View more questions Search