    Effluent pump pit vent
    I have an effluent pump in my lower level. When I had the house built several yrs. Ago I hired a plumbing company to do all the plumbing. My effluent pump had to be replaced after seven yrs. And it was at this time that I found out there was a vent hole in the pit cover which was capped off with about a four inch piece of plastic pipe placed into the hole with a plastic cap sealing same. The plumber said that this is acceptable and sees no need to vent. If it does in fact need to be vented what would be the proper way. He was talking about ventling it into the main discharge pipe from the house to the septic tank.Is this acceptable?
    solkonnichi2864's Avatar
    solkonnichi2864 Posts: 2, Reputation: 1
    New Member
     
    #2

    Jan 31, 2010, 03:56 PM

    I have an effluent pit with pump in my lower level. I have a septic system. When I had the house built the plumber placed a four inch capped pipe into the vent hole and said it was not necessary to vent same. He said if he did vent it, it would have to be run into the main drain pipe that goes out to the septic system. Is he right? The house was built in 2003 and I have just found this problem because the original pump recently had to be replaced.
    massplumber2008's Avatar
    massplumber2008 Posts: 12,832, Reputation: 1212
    Senior Plumbing Expert
     
    #3

    Jan 31, 2010, 04:43 PM
    Hi Solkonnichi:

    Nope... the plumber is feeding you bad info.! Obviously, the first plumber did not pull a plumbing permit for this work... correct?

    All sewage ejectors require a separate vent to be piped up and out the roof individually. Some local plumbing codes will allow you to connect an ejector pit vent into the existing house vent stack just before it goes out the roof, but that is an exception and usually requires the plumbing inspector's approval. Most inspectors will not allow this.

    Further, if that ejector pit wasn't vented then for what it is worth I'm pretty sure that the pit has been venting through the fixtures in the bathroom that this pump serves. This means that sewer gasses have been getting into the bathroom and simply put... that's not a healthy thing!

    Pipe the 2" vent up and through the roof or at a minimum connect it into the existing vent stack about 2 feet below where the roof penetrates the roof. In cases like your I have run a 2" vent up through closets to get to the attic... worked pretty good without having to tear walls open.

    Let us know if you would like to discuss more... OK?

    MARK

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Sump pump parts (Pit Viper) [ 5 Answers ]

Need parts for a PIT VIPER sump pump by ACE. The pump works great but the float is half filled with water and does not turn the unit on or off! I currently have a make shift styrofoam float attached but need a replacement float from the company "Pit Viper". Are they still in business and can...

Sump pump pit? [ 4 Answers ]

Thank you for looking at my question. I have a sump pump in the basement and I decided to try to clean the pit. When I drained most of the water I started to poke around to see what kind of bottom there was. That's when I noticed that the bottom seems to be of concrete and so are the walls. The...

Laundry Pump vent hookup. How? - no vent access [ 9 Answers ]

I have a Laundry Tray Pump System connected to my wash tub in my fifteen year old townhome's basement. I was recently informed that it was not properly installed because I never connected the vent pipe from the pump. I had some one look at it and was told that the house's vent system (which...

Drain tile and sump pit and pump [ 3 Answers ]

Can anyone be more specific as to install drain tile and sump pit. Like how deep should I dig down around inside of foundation.How far from the foundation walls. Should I come out and how far from the wall should I place the pipe. Can I use 4 in plastic flex pipe? Should the concrete be cut with...


View more questions Search