    Failed inspection
    Replaced a 4" cast vertical waste pipe with 4" PVC and replumbed 3 bathrooms. Inspection went well except the inspector wants me to install a test tee? At the base of the replaced stack for a water test. I have plugged all the drain openings, now I assume there is some type of tee that has a valve in it to shut the trunk line down so we can fill it with water to see if it holds. Then after that I guess you remove the test tee?
    What does he mean asking for a water test? And where to find a 4" test tee?
    massplumber2008's Avatar
    massplumber2008 Posts: 12,832, Reputation: 1212
    Senior Plumbing Expert
     
    #2

    Jan 29, 2010, 12:56 PM
    Hi Topcat:

    He is talking about installing a test tee... also called a dandy cleanout (see images) at the base of the stack... and it stays there permanently.

    Once the test tee is installed you will need to purchase a cherne seal test plug (about $30.00... see images) and install that into the test tee and pump it up as stated on the plug. Now you can introduce water to the system.

    These can be found at any local plumbing supply supply or even here online:

    http://aolsearcht4.search.aol.com/ao...ntshopping.com

    In my area the test will be to fill the entire system with water to the point that it flows out the roof vent. Obviously, you would be filling the pipes from the roof... ;)

    You may need other plugs/caps to do this test to the inspector's satisfaction.

    Let us know if you want to discuss more... OK?

    MARK
    Attached Images
        
    topcat6's Avatar
    topcat6 Posts: 40, Reputation: 2
    Junior Member
     
    #3

    Jan 30, 2010, 07:44 PM

    Thanks for the detailed explanation. When installing this tee at the base of the stack, would you place a clean out above it or below it? Or can this double as a clean out?
    massplumber2008's Avatar
    massplumber2008 Posts: 12,832, Reputation: 1212
    Senior Plumbing Expert
     
    #4

    Jan 31, 2010, 05:38 AM
    The test tee is the cleanout. Once the test is completed you will add some pipe dope to the threads of the test tee cap and screw it back into the test tee.

    Another name for the test tee is a dandy clean out.

    MARK
    speedball1's Avatar
    speedball1 Posts: 29,301, Reputation: 1939
    Eternal Plumber
     
    #5

    Jan 31, 2010, 08:07 AM
    Quote Originally Posted by ;
    Once the test tee is installed you will need to purchase a cherne seal test plug (about $30.00... see images) and install that into the test tee and pump it up as stated on the plug. Now you can introduce water to the system.
    These can be found at any local plumbing supply supply or even here online:
    Another less expensive test plug would be a inflatable test ball, (see image). Youinsert the ball and pump it up with a bicycle pump.
    As Mark stated, we fill our stacks from the roof until they over flow. Leave them over night and call for a inspection the next morning.
    Another name for the test tee is a dandy clean out.
    And yet another is a "inspection tee"
    Good luck, Tom
    Attached Images
     
    massplumber2008's Avatar
    massplumber2008 Posts: 12,832, Reputation: 1212
    Senior Plumbing Expert
     
    #6

    Jan 31, 2010, 09:45 AM
    Hi all...

    Actually, Tom... A 4" Cherne seal test plug ($26.00) is cheaper than a regular 4" regular test ball ($28.00). ;)

    And an especially nice feature of the cherne seal test ball is that you can release the air from the ball and the water flows by without any fingers getting pinched or any water getting on the floor because you don't have to remove the plug/cap to drain the pipes.

    I remember one time when I released a regular test ball from a test tee and the darn thing wouldn't release as the head of pressure from above forced it down into the pipe... ended with 3 floors of test water out onto the basement floor before I could get it out... and I was soaked. My boss was NOT impressed! LOL!

    MARK

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Electrical inspection [ 9 Answers ]

I passed the final inspection today on the self wiring I did on my cabin. This site was a big reason why I passed with flying colors. Thanks to everybody...

2002 RAV4 inspection failed 'NOT READY' [ 3 Answers ]

My 2002 RAV4 never had any problem. One year ago battery went down when lights were left in the car for long time and needed jump start. Battery is still original, may be is that the battery need to be changed. Thanks for advise in advance.

Eviction because of failed property inspection [ 2 Answers ]

I am currently on a month to month basis with my leaseholder/apt complex. My rent is paid in full and is NOT in default We recently had an housing inspectinon in which the property manager says my dwelling is violation of the landord/tenant agreemant,(too much clutter in home) and they could evict...

Home inspection [ 3 Answers ]

I bought a home in July , a home warranty was purchased. I did not have a home inspection done. I need to know what is check in heating /ac unit . If a home inspector would have checked if a 2"X8" crack in the heat exchanger or would he just cut unit on to see if it works?:mad:

Failed toilet vent inspection( Help!) [ 11 Answers ]

We have a newly constructed building(bathhouse) added to or home septic system.It has a shower stall,toilet ,sink,kitchen sink and hot water heater added on.Every thing passed inspection except the toilet(even the waste line to the septic passed).The inspector said its NOT holding pressure.It...


View more questions Search