    Sink vent
    My bathroom sink emits an odor after having big remodel. The vent is connected above the trap on the sink side. I think the vent should be downstream of the trap. What's right?
    massplumber2008's Avatar
    massplumber2008 Posts: 12,832, Reputation: 1212
    Senior Plumbing Expert
     
    #2

    Jan 26, 2009, 05:11 PM
    Hi JKM97:

    The AAV must be downstream of the ptrap as in my pictures below.

    It can be installed on the vertical or the horizontal, but must be after the ptrap... ;)

    Let me know if this is your case or not...

    MARK
    Attached Images
     
    mygirlsdad77's Avatar
    mygirlsdad77 Posts: 5,713, Reputation: 339
    Plumbing Expert
     
    #3

    Jan 26, 2009, 05:23 PM

    If vent is connected between sink and trap, you have a problem. You are right when you say vent should be located downstream of trap. Look at Marks drawings, and if you could post a pic of your setup, it would really help. If things are the way they seem, you need to get the person who did your plumbing back in and have them fix it. I really want to see some pics of your setup. If vent is taken off before trap, this is no small error. This would be extreme lack of knowledge of plumbing and the person who installed it this way, should not ever do plumbing again... Danger to health.
    massplumber2008's Avatar
    massplumber2008 Posts: 12,832, Reputation: 1212
    Senior Plumbing Expert
     
    #4

    Jan 26, 2009, 05:57 PM
    Hey Lee (MGD77)... I got to agree! I would love to see a picture of this setup! I love pictures of silly mistakes so called plumbers make. Here's a fun pic. Just to add to the mix.. see below.

    I have more... ;)

    JKM... any chance you can post pic. Of yours as requested?

    Thank you!

    MARK
    Attached Images
     
    mygirlsdad77's Avatar
    mygirlsdad77 Posts: 5,713, Reputation: 339
    Plumbing Expert
     
    #5

    Jan 26, 2009, 07:26 PM

    The worst part is, I've seen something like this before, I quess they call it a horizontal trap.. lol

    And they wonder why they are getting a stink from the sink, hmmmm.
    jkm97's Avatar
    jkm97 Posts: 4, Reputation: 1
    New Member
     
    #6

    Jan 27, 2009, 01:08 PM
    Quote Originally Posted by massplumber2008 View Post
    Hi JKM97:

    The AAV must be downstream of the ptrap as in my pictures below.

    It can be installed on the vertical or the horizontal, but must be after the ptrap...;)

    Let me know if this is your case or not...

    MARK
    Sorry. The pipe I thought was a vent turned out to be the condensate drain from the air conditioner.
    jkm97's Avatar
    jkm97 Posts: 4, Reputation: 1
    New Member
     
    #7

    Jan 27, 2009, 01:10 PM

    Sorry. It turned out that the pipe I thought was a vent was the condensate line from the air conditioner.
    mygirlsdad77's Avatar
    mygirlsdad77 Posts: 5,713, Reputation: 339
    Plumbing Expert
     
    #8

    Jan 27, 2009, 04:09 PM

    Have you located origin of smell yet?
    Milo Dolezal's Avatar
    Milo Dolezal Posts: 7,192, Reputation: 523
    Plumbing Expert
     
    #9

    Jan 27, 2009, 04:49 PM

    Mark: LOL ! That photo is very funny !
    massplumber2008's Avatar
    massplumber2008 Posts: 12,832, Reputation: 1212
    Senior Plumbing Expert
     
    #10

    Jan 27, 2009, 05:03 PM
    If you liked that one Milo... here's another fun one... :)

    Imagine the work it took to fix this mess?

    Thanks...

    MARK
    Attached Images
     
    mygirlsdad77's Avatar
    mygirlsdad77 Posts: 5,713, Reputation: 339
    Plumbing Expert
     
    #11

    Jan 27, 2009, 05:21 PM

    What, I don't see any problem,, structural floor joist are really only for looks, just cut them out and go(plumbing is more important than carpentry)

    But really, what the hell were they thinking(most likely not thinking, or not capable of thinking) The general contractors I work with would have hauled me out back and beat me severely, then made my boss pay for extensive repairs(on the house, not me)

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Relocating Sink Drain/Vent to Dedicated Stack Serving Kitchen Sink & Dishwasher [ 3 Answers ]

I am relocating an upstairs vanity sink from one wall to another (also going from single to double bowl). Rather than relocate the drain and vent pipe, I am hoping that I can tie into a 1-1/2" copper vent pipe that is located right behind the vanities intended location. The copper vent pipe is from...

Sink vent [ 5 Answers ]

I may have goofed... I installed a new sink, drain is 1 1/2" but forgot a vent for it... but the sink drain is located 9 ft from the main 3 ft drain... sheet rock is up and painted. Will I have any drain problems... suggestions please.. thank you

Sink Vent [ 3 Answers ]

We had a small leak on the other side of the vent on the drain pipe on the kitchen sink. No more leak, but the cesspool smell is horrible. Any ideas? Thanks!

Laundry Sink Vent [ 3 Answers ]

I would like to place a laundry sink in the basement. The location in question is under the kitchen. I can tie into the drain pipe from the kitchen which would run vertically, right next to the laundry sink. However, the nearest point where I could attach a vent line is about twenty feet from...

Kitchen Sink/Laundry Sink Drain Vent Non-exist [ 3 Answers ]

The set-up from kitchen sink leading down to drain to basement: 1. Kitchen sink - (R side) - connected to a P drain I think you call it -PVC-, connected to a "metal" T, which has a Studer vent gizmo attached to the top of it, then draining into a metal pipe straight down to the drain in the...


View more questions Search