    Rheem Critirion II Intermittent turn on
    I have looked at the other discussions about the Rheem II and have an additional problem.

    The Heater (only heater I don't have AC) tends to be a little troublesome at times. I tested the vacuum for the blower relay as suggested in another forum. I hear clicks both ways.

    This is what I have to do sometimes to get it to come on. Like a old coke machine I have to give it a good wallup on the side of the unit then I hear a click and it comes on.

    Why?

    Sometimes it will come on like it is supposed to without giving it a smack. All lights Power On and Flame are lighting up like they are supposed to after I smack it. Before I smack it I get the Power and the On light flashes 4 times over and over.

    Bill
    hvac1000's Avatar
    hvac1000 Posts: 14,540, Reputation: 435
    Heating & Air Conditioning Expert
     
    #2

    Dec 15, 2008, 01:12 PM
    Bad grounds. What does the code on the inside of the blower door panel say 4 flashes mean? Post back
    cat3rn's Avatar
    cat3rn Posts: 2, Reputation: 1
    New Member
     
    #3

    Dec 16, 2008, 11:37 PM
    Quote Originally Posted by hvac1000 View Post
    Bad grounds. What does the code on the inside of the blower door panel say 4 flashes mean? Post back
    It says that 4 blinks followed by a 2 sec pause indicates that the pressure switch is closed. I think when I smack it it opens up and then turns on. Believe that I tested it by removing the hose and blowing and sucking on it and got clicks both ways.
    hvac1000's Avatar
    hvac1000 Posts: 14,540, Reputation: 435
    Heating & Air Conditioning Expert
     
    #4

    Dec 17, 2008, 12:55 AM
    Bad switch

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Rheem furnace blower motor won't turn on [ 2 Answers ]

My furnace blower motor will not turn on. The troubleshooting guide says to replace blower motor but the diagnostics says the Limit Switch is Open any ideas

14.5 hp Briggs I/c ohv very slow and intermittent turn over [ 1 Answers ]

The engine is on a 2000 model yard machine 42" cut riding mower and was given to me. I was told that it probably just needed the valves adjusted as had been done before and it ran fine. Well, I adjusted the valves; intake - .005", exhaust - .007", with the piston at 1/4" top dead center. The...

Intermittent turn signals [ 4 Answers ]

I have a 2001 jeep cherokee the turn signals worked when they felt like it.I replaced the flasher and for two weeks no problem.Now The signals work randomly.Any ideas.Thanks


View more questions Search