    Plumbing Re-routing
    Hi. I've embarked on a renovation project which consists of knocking down a non-load-bearing wall to combine an existing (2-piece) ensuite with a walk-in closet. Our objective is to use the additional space to expand the existing ensuite bathroom, most notably add a walk-in shower. This expanded room (the wall has already been removed) is situated adjacent to another full bathroom serving the other 2nd floor bedrooms. That said, all the plumbing pipes, drains, and vents are in the wall and are now exposed when I removed a piece of greenboard. In addition, plumbing for the existing ensuite is also in place.
    I've made a drawing to reflect re-routing of supply water pipes and the addition of new DWV to serve the new walk-in shower as well as the relocation of the vanity.
    I realize codes are different from jursidiction to jursidiction but I'm looking for professional feedback. Does anyone see areas of concern?
    Attached Images
  1. File Type: pdf Plumbing rerouting.pdf (259.2 KB, 537 views)
  2. speedball1's Avatar
    speedball1 Posts: 29,301, Reputation: 1939
    Eternal Plumber
     
    #2

    Jun 6, 2006, 03:46 PM
    Quote Originally Posted by JSD
    Hi. I've embarked on a renovation project which consists of knocking down a non-load-bearing wall to combine an existing (2-piece) ensuite with a walk-in closet. Our objective is to use the additional space to expand the existing ensuite bathroom, most notably add a walk-in shower. This expanded room (the wall has already been removed) is situated adjacent to another full bathroom serving the other 2nd floor bedrooms. That said, all the plumbing pipes, drains, and vents are in the wall and are now exposed when I removed a piece of greenboard. In addition, plumbing for the existing ensuite is also in place.
    I've made a drawing to reflect re-routing of supply water pipes and the addition of new DWV to serve the new walk-in shower as well as the relocation of the vanity.
    I realize codes are different from jursidiction to jursidiction but I'm looking for professional feedback. Does anyone see areas of concern?
    Your drawings refused to download. I disengaged my firewall so it wasn't that.
    Try uploading them again. Thanks, tom
    JSD's Avatar
    JSD Posts: 4, Reputation: 1
    New Member
     
    #3

    Jun 7, 2006, 06:48 AM
    OK. Here's the file again, only this time in a jpeg format.
    Attached Images
     
    speedball1's Avatar
    speedball1 Posts: 29,301, Reputation: 1939
    Eternal Plumber
     
    #4

    Jun 8, 2006, 07:09 AM
    Basically your lay out looks OK. Our codes dictate 4" for toilets under a slab and 2" for drainage and vents. I hope the revent system teis back into the 3" vent stack because if it don't all you have is a closed system with no vent outlet. Also you need to rethink your fittings. Your thoughts? Tom
    JSD's Avatar
    JSD Posts: 4, Reputation: 1
    New Member
     
    #5

    Jun 8, 2006, 07:41 AM
    Hi Tom. I'm quite pleased with your assistance. Jurisdictional code differences aside, I think I'm ready to proceed with a permit application.
    Just to be sure, this is an image of what I'm calling (on my drawing) a wye/tee. Is this the same thing as a drainage tee or is there a difference?
    Although not too clear on my drawing, this vent system does tie into the 3" vent stack leading upward to the roof.
    Attached Images
     
    speedball1's Avatar
    speedball1 Posts: 29,301, Reputation: 1939
    Eternal Plumber
     
    #6

    Jun 8, 2006, 11:01 AM
    What you have pictured is a drainage tee, (see image) and is not the same as a Tee-Wye Combination,(see image). I would change some of my terms before I submitted the drainage for approval. The fitting terms are misleading.
    Although your basic layout looks good and I can find no outstanding mistakes, in my area, (Tampa Bay) code does not allow 3" and 1 1/2" under the slab and most of our local codes call for 2" vents plus one 3" vent per house.
    Check with your local Building Department.
    Good luck, Tom
    JSD's Avatar
    JSD Posts: 4, Reputation: 1
    New Member
     
    #7

    Jun 8, 2006, 11:35 AM
    I certainly will. Thanks for the clarification. I'll modify my terms right away to avoid being misleading.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Advice needed on sizing/routing PEX lines [ 10 Answers ]

I am beginning to replace the 53 year old copper lines in my house with PEX as I am building a bathroom in the basement. I want to put in a manifold to separate some of the lines and give a central location for shutoff controls. Running individual lines to every fixture could be a bit expensive...

Problem with IP routing table! [ 1 Answers ]

My IPGateway is NSG4000 (made in Taiwan), in its static routing table I want to assign IP 0.0.0.0 and Subnet mask 0.0.0.0. But I don't know why it can't assign that IP and SM :confused: . Are there any other way to assign IP and SM 0.0.0.0? Please help me! Thanks!

Plumbing [ 5 Answers ]

Bought an old house - over 50 yrs old in town - sewer problems from day one - Backed up sewage - had plumber in and of course paid out a large sum of money for a continuous problem. Long story short - had a bunch of roots in the concrete pipes. Now that seems to be fixed - I hope. Problem now is...

Plumbing [ 1 Answers ]

How do I get rid of air in my domestic water system in the house, please? I have just installed a new shower and the groaning noise now must be disturbing my poor neighbours. Thanks in anticipation.

Plumbing [ 1 Answers ]

How do you put in a rubber/ spring in the hole under the cartridge faucet? Position of Rubber and spring?


View more questions Search