    #1

    Apr 29, 2006, 03:43 PM
    treborc Rough In
    treborc
    New Member Join Date: Apr 2006
    Posts: 8

    Sorry for the pm but I have some pictures that may be a bit to big for the forum so I figured better to pm you than post and slow down board.

    You have provided a lot of help to me so far and I want to run what I am about to do past to you to make sure it all correct.

    Below you will find two drawings of the ruff layout of my project. And what I am now going to start ruffing in the plumbing on I just wanted to make sure that the way I have it is going to be OK.

    First is a drawing of how I was planning on the drain pipe. Black is 3 inch drain red is 2 inch drain and green is 1 /12 vent I am sure your going to tell me that needs to be 2 inch though.

    For the lav and bath 2 inch pipe I planned on dropping it down into the 3 inch drain from the top not sure if this is how I am supposed to do it or if I am supposed to come in on the side of the 3 inch? Any advise you can give me on what fitting to use etc is greatly needed. Still a bit confused on how to vent the toilet can I just take and put in a 3 x3 x2 just under the flange to vent it? Sorry to be such a pain.
    speedball1's Avatar
    speedball1 Posts: 29,301, Reputation: 1939
    Eternal Plumber
     
    #2

    Apr 29, 2006, 04:34 PM
    Unless local codes call for a individual vent on the toilet it's wet vented by the lavatory vent. Would it be possible to drop the 3" low enough to run the tub drain over it and tie it into the lavatory drain? If you could configure it that way you could get by with one 2" vent off the lav. If not you will have to move the tub vent downstream from the trap. We will get into fittings when the drainage is laid out. Regards, Tom
    treborc's Avatar
    treborc Posts: 16, Reputation: 1
    New Member
     
    #3

    May 4, 2006, 12:37 PM
    help with layout of bathroom plumbing
    Below you will find two drawings of the ruff layout of my project. What I am now hoping to start ruffing in the plumbing. If someone could provide me with what parts they think I would need it would be much appreciated.

    Also the lav is a pedistal on an exterior wall the wall is a 2 x 6 wall but we live in a area that experiences winter my question on that is should I be concerned about putting the pipes inside this wall about freezing?

    First is a drawing of how I was planning on the drain pipe. Black is 3 inch drain red is 2 inch drain and green is 2 inch vent.



    This one is of a 3d view of what it would look like in the basement.



    For the lav and bath 2 inch pipe I planned on dropping it down into the 3 inch drain from the top not sure if this is how I am supposed to do it or if I am supposed to come in on the side of the 3 inch? Any advise you can give me on what fitting to use etc is greatly needed. Still a bit confused on how to vent the toilet can I just take and put in a 3 x3 x2 just under the flange to vent it? Sorry for so many questions just want to make sure I do it right the first time.
    speedball1's Avatar
    speedball1 Posts: 29,301, Reputation: 1939
    Eternal Plumber
     
    #4

    May 4, 2006, 02:28 PM
    I have studied your lay out. If you could possibly lower the main enough to get either the lavatory or the shower drain line over it I can get you by with one vent for the entire group. This will hinge on the elevation of the main under the floor. How it would work is lower the main down enough to slip the 2" shower drain line over it and connect to the lavatory drain where it will be wet vented by it. The lav drain could then 45 down and connect to the main.
    This will save you the hassle of installing three vents where one will do.
    As I've stated we'll talk fittings when the job gets laid out. Regards, Tom
    treborc's Avatar
    treborc Posts: 16, Reputation: 1
    New Member
     
    #5

    May 4, 2006, 04:47 PM
    Yeah I can drop it however far it needs to go that room is nothing but a storage room in the basement is nothing but storage in the firstplace.
    speedball1's Avatar
    speedball1 Posts: 29,301, Reputation: 1939
    Eternal Plumber
     
    #6

    May 5, 2006, 06:38 AM
    OK,

    Start at the toilet. From the flange drop the quarter bend low enough to slide the 2" shower drain over the 3" main branch. I have Xed out the drains and vents and have drawn in the new configuration, (see image). If it meets with your approval then we can c began to make a material list. Sound like a plan? Tom
    treborc's Avatar
    treborc Posts: 16, Reputation: 1
    New Member
     
    #7

    May 5, 2006, 07:37 AM
    Looks good but is it an issue to have the lav hooking into the shower and the shower vents instead of the Lav.
    speedball1's Avatar
    speedball1 Posts: 29,301, Reputation: 1939
    Eternal Plumber
     
    #8

    May 5, 2006, 08:05 AM
    Quote Originally Posted by treborc
    Looks good but is it an issue to have the lav hooking into the shower and the shower vents instead of the Lav.
    If you will look on the plan you will see the vent is located off the lavatory and not the shower.
    The shower connects into the lavatory drain where it will be wet vented by the lavatory vent. I took your drawing over to paint and attempted to change the background to white so I could draw in changes but I couldn't so this is the best I can do. This is a rough drawing of what I want to do. The shower drain will have to be reconfigured so it enters the lavatorfy drain at a better angle
    Is there any chance that you could change the blue background to white on the print?
    That way I could scan a master drawing in without the drains so I could do a layout?
    Cheers, Tom
    treborc's Avatar
    treborc Posts: 16, Reputation: 1
    New Member
     
    #9

    May 5, 2006, 08:40 AM
    The way you have it looks fine I will look to see if I can change the background color when I get home from work. :D
    treborc's Avatar
    treborc Posts: 16, Reputation: 1
    New Member
     
    #10

    May 9, 2006, 01:59 PM
    This one work?

    speedball1's Avatar
    speedball1 Posts: 29,301, Reputation: 1939
    Eternal Plumber
     
    #11

    May 9, 2006, 03:52 PM
    Thanks,
    Works for me. I'm tied up today so it will late afternoon or tonight before I get back to you. Cheers, Tom
    speedball1's Avatar
    speedball1 Posts: 29,301, Reputation: 1939
    Eternal Plumber
     
    #12

    May 11, 2006, 11:58 AM
    Start at the toilet. From the flange drop the quarter bend low enough to slide the 2" shower drain over the 3" toilet branch. You may then 45 over to a 2" combination wye and 1/8th bend on the lavatory drain to connect. This configuration will do away with 2 vents and the need to revent them,(see image). The shower and the toilet will be wet vented by the lavatory vert. More questions? I'm as close as a click.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

DWV rough-in [ 5 Answers ]

I'm starting a long delayed home construction in a rural area with no plumbing codes in force. I plan on laying out the under slab DWV lines. Below in my amatuerish plan which I'm sure has glaring red flag issues that I need to adjust. Can you offer some input ? The main waste line run is about 40...

Rough feet... [ 3 Answers ]

Hi, My feets are getting roughs specially heels can anybody tell me any remdy for this or any type of medicine for this broken heels... thanx a lot

Please help me get over this rough period [ 74 Answers ]

So the other day my girlfriend told me she needed her space. We got together when she was 18 and I was 23. Now, at the time, I had already gone through a couple of serious relationships, as well as that whole peroid of my life where I went out and had fun while I was single. Since my girlfriend is...

Rough in under slab [ 1 Answers ]

Hey Tom, I am currently renovating my mother’s bathroom; it was very out of date. Here’s my problem, she lives on a slab. I was hoping you might be able to tell me if my changes in the plumbing will work. I have attached two pictures, one of the old plan and one of the proposed plan, I have tried...

Slab Rough-In [ 29 Answers ]

I am embarking a project to remodel a half bath to a full bath on the ground floor of a high ranch. (on slab). After getting a couple estimates on the rough-in plumbing, and seeing that they were more than anticipated, I think I am going to give it a shot. I do most everything….framing, drywall,...


View more questions Search