    Basement sewage pump circuit
    I live in NJ. Does the plumbing code indicate that a basement sewage pump has to be on a separate circuit? Or, can it be on the same 20 amp circuit as the bathroom it services. The pump is rated for 15 amps.
    massplumber2008's Avatar
    massplumber2008 Posts: 12,832, Reputation: 1212
    Senior Plumbing Expert
     
    #2

    Apr 7, 2008, 04:00 AM
    Hi JK

    Plumbing code does not say anything to do with electrical code. This question may do better over at electrical.

    However, in all my years of installing these ejector pumps almost every one had its own dedicated circuit. Some of these circuits had G.F.C.I. protection... others didn't. BUT, as said, almost every one had its own dedicated circuit.

    Sorry, that's all I have for now. I am sure others will be in with opinions as well. I will try to see if we can move you over to electric so they can answer the CODE question asap!

    Good luck! Mark

    .
    Credendovidis's Avatar
    Credendovidis Posts: 1,593, Reputation: 66
    -
     
    #3

    Apr 9, 2008, 02:20 AM
    I would say that (besides IF there are rules for a separate circuit) it much depends on what else you run in that same circuit. Do you have only lights, or do you have any (other) appliances on that same circuit?
    Specially any possible start-up motor current could be a problem.
    That saying : a pump rated for 15 Amps can have a starting peak current double of that, though this is only for less than a second.
    It would be wise to upgrade your breaker to accommodate that start-up current pulse! Say to 30+ Amps.
    ;)
    stanfortyman's Avatar
    stanfortyman Posts: 5,598, Reputation: 279
    Electrical & Lighting Expert
     
    #4

    Apr 9, 2008, 04:11 AM
    A 15A pump would need a dedicated 20A circuit regardless of where it is.
    It especially CANNOT be on a circuit with bathroom receptacles.
    Credendovidis's Avatar
    Credendovidis Posts: 1,593, Reputation: 66
    -
     
    #5

    Apr 10, 2008, 03:37 AM
    Quote Originally Posted by stanfortyman
    A 15A pump would need a dedicated 20A circuit regardless of where it is. It especially CANNOT be on a circuit with bathroom receptacles.
    And amen (... so be it... ) to that!
    ;)

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Oatey in line vent for sewage pump in the basement [ 14 Answers ]

I am in th process of adding a basement bathroom in my house.I have hired a lic plumber. The plumber is running vent line to the sink the toilet and the shower (Lets call it vent line 1).He than connects this vent line 1 to the vent line coming out of the sewage ejector pump (Vent line 2).He...

Sewage Ejector Pump in a Basement [ 9 Answers ]

Hello all I am new to this board so forgive me if this has already been asked. I am in the process of adding a basement to our basement. We have a septic system with the discharge pipe about 3 feet above the floor. Several questions. I want to add a Toilet, sink and tub. What all has to be vented....

Sewage Smell in Finished Basement with Ejector Pump [ 6 Answers ]

We have a sewage smell in our basement that we finished and added a bathroom. It has an ejector pump and we have sealed off the crock top with caulk and wax. The smell is not all the time and is very inconsistent. We have city sewage. We have tried everything with not luck. The only thing that we...


View more questions Search