    Lennox G51MP won't light
    [FONT=Verdana][COLOR=#191970]White deposits collect in the pressure taps on the CAI/header box where the prove switch hoses connect. This is preventing the burner from lighting. I pull off the hoses, blow them out, and clear the pressure taps with a wire. Furnace works again for a few days till the build up returns. I've been told that the build up is possibly sulphur, which is a result of the combustion of the propane. What can I do to resolve this problem.[/COLOR][/FONT]
    ma0641's Avatar
    ma0641 Posts: 15,675, Reputation: 1012
    Uber Member
     
    #2

    Sep 24, 2015, 02:16 PM
    Doubt sulfur from propane. There is a minuscule amount of Mercaptan which is sulfur bearing but not to the extent you indicate. Is this a condensing furnace? Sounds more like mineral deposits from water.
    snoracer's Avatar
    snoracer Posts: 2, Reputation: 1
    New Member
     
    #3

    Sep 24, 2015, 08:29 PM
    I paid a visit to a Lennox dealer (not the one who did my install), explained my problem. He's the one who told me about the sulfur deposit issue, and that Lennox actually issued a fix. Some Teflon inserts that are supposed to be slippery and not allow the deposits to stick. Spoke to my installer, he had already tried this fix. I have a 3rd Lennox dealer tech coming out to the house tomorrow to check that this furnace was installed correctly, and adjusted properly. Thanks for your reply.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Lennox G51MP gas furnace [ 0 Answers ]

I have a Lennox G51MP Gas Furnace. I get a hint of gas smell from the air vent closest to the furnace during the period from when the furnace heat cycle is initiated by the thermostat to when the air blower is turned on. Has anyone experienced this problem? If so what was theproblem?

Lennox G51MP Furnace goes out after an hour [ 1 Answers ]

My 7 year old Lennox G51 furnace has an intermittent failure where if it runs for more than 1 hour continuously the flames go out, it begins blowing cold air and the status LEDs indicate that it has entered a Watchguard state. This failure is repeatable and always happens after 1 hour. When I...

My lennox furnace won't light the fan blows the pilot light lights it clicks but won't [ 0 Answers ]

My furnace will not light pilot light lights, it clicks to start but burners will not ignite fan also works

Lennox g51mp no hot air [ 2 Answers ]

My LENNOX Gas Furnace-High Efficiency G51MP Series is 4 years old. The furnace used to work perfectly. We went away for the weekend set the thermostat at 62 degrees and came back to a cold house last night of 53 degrees and cold air coming out. We check the filter (brand new) and the intake is...

Lennox G51MP burners will not ingnite? [ 0 Answers ]

My Lennox G51MP burners will not ingnite. My code is slow flashing R LED. Earlier today the burners would ingnite and then would go out immediately. Cleared the intake valve from snow. Started up. It was a different code then. Now the glowing yellow light through the peep hole will not even start...


View more questions Search