    Condenser Fan Starts but turns slowly and stops
    Hi, my outside unit quit working the other day. It is an ICP 5 ton I believe. I I found and replaced the blown capacitor (looked like a dropped soda can). Now, the fan will come on but turns slowly and eventually stops. The compressor is coming on and cool air does blow out of the vents in the house while the condenser fan is running.

    What is the most likely next step? I was thinking the fan motor
    skipper1080's Avatar
    skipper1080 Posts: 7, Reputation: 1
    New Member
     
    #2

    Jun 24, 2015, 03:44 AM
    that is the next logical step. Remember you will have to change capacitor again as the fan motors have different values of capacitance.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

2007 troy bilt pony Has new drive belts starts going but slowly stops [ 1 Answers ]

It will start moving but slowly stops. It has new drive belts.

2007 troy bilt pony Has new drive belts starts going but slowly stops [ 0 Answers ]

It has new drive belts. Will start going but slowly stops

When our central heat turns on the motor starts then stops a lot while the fan stayson [ 0 Answers ]

When our central heat turns on the motor starts then stops over and over. The fan stays on during this. It also seems that the air coming out of the ducts is cold. Help!

Condenser Fan stops and starts [ 1 Answers ]

I have a Bryant system and I have replaced the cap and the fan motor on the outside unit. My question is this, should the condenser fan always run when the pump is on or does it regulate the temperature and turn the fan on as needed. I thought it ran constantly as long as the unit was on. ...


View more questions Search