    Forced hot air supply placement in the ceiling
    I am putting in new gas forced hotair furnace and ductwork. House is one story and on a concrete slab so duct work must go in attic. The installer suggests putting the supply registers in the center of each room with 360 degree air diffusers on all registers. And central cold air return in the center of the house ceiling. The house is quite small at 900 SF.
    I don't agree with that placement of the supply registers and thing they should be placed nearer the outside walls with a 180 degree diffuser and the central cold air return at the bottom of inside wall.
    Which way would end up being the more efficient way>
    Thanks
    mygirlsdad77's Avatar
    mygirlsdad77 Posts: 5,713, Reputation: 339
    Plumbing Expert
     
    #2

    Sep 28, 2012, 03:16 PM
    I agree with your idea. Supplies should be located near ouside wall over windows and outside doors, just as they would be if they were in the floor. And return/s on inside wall/s near the floor. You will be fine with either the 360 or 180 diffusers.
    stoningham's Avatar
    stoningham Posts: 2, Reputation: 1
    New Member
     
    #3

    Sep 28, 2012, 07:37 PM
    Thank you for the reply.
    When I questioned the installer about not putting them near the outside walls he used phrases like "you won't know the difference","thats the way I have always done it" and a couple more meaningless phrases that raised a red flag to me.
    Now I will try to find some sort of formula/directions on how much distance from the outside wall with what style diffuser so the heated air can flow down the wall without creating a draft
    Thanks again for the reply

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

My gas forced hot air furnace blows out hot air sometimes when I connect wires help [ 2 Answers ]

Can you help me understand what might be the problem

Water heater with damper or forced air supply? [ 1 Answers ]

So much heat is lost up the vent (flue) 24/7, is there a way to place a damper on the water heater? As a chimney sweep on the roof after dark in winter months, I have warmed my hands on the lost heat. Air heated inside the water heater center tube rises. As it flows out, it pulls new cool air...

Forced Hot Air *Electric [ 2 Answers ]

I have forced hot air and the unit outside has been frosted during most of the winter even on days that aren't so cold(50 degrees) the air coming out of the vents are cold and the temp inside will not get any warmer than 60 and the therm is set at 74... please help

Forced Hot Air Heater [ 1 Answers ]

I've noticed lately that my forced hot hair heating system is louder than it used to be. I have to turn up the TV when it goes on. I don't recall it ever being that noticeable or loud. Any suggestions on what it could be?


View more questions Search