    Miller CMF Series 80-PG Gas Furnace Blower
    I think the Miller CMF Series 80-PG Gas Furnace is around 20 years old. I need to know about the ground wire to the blower motor. Does it go to the door switch or to the heat limit switch?
    labman's Avatar
    labman Posts: 10,580, Reputation: 551
    Uber Member
     
    #2

    Jan 26, 2007, 09:31 PM
    The white wire from the blower motor needs to be connected to the white wire from the house wiring perhaps at the door switch. The green wire from the blower motor needs to be connected to the bare wire from the house wiring, perhaps by both being connected to the metal frame of the furnace. The white is really called a neutral, not ground.
    NorthernHeat's Avatar
    NorthernHeat Posts: 1,455, Reputation: 132
    Ultra Member
     
    #3

    Jan 27, 2007, 10:18 AM
    It won't go to the door switch since that should be 120V hot not neutral.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Miller Oil Furnace [ 3 Answers ]

I have a miller oil furnace that was installed in July of 2006 it has been running just fine until now I have power to it but it won't run. I can get the fan to start but when I hit the reset button all I get is the blinking light. Can you help:(

Gas Furnace Blower Motor [ 6 Answers ]

I have an old Rheem gas furnace. My fan blower motor stopped working. I had Sears order me a new one. The installer walked away, giving up because he couldn't get the old motor out of the housing. I got it out and installed the new one myself. Everything turns freely. I made the furnace turn on and...

Miller oil Furnace [ 10 Answers ]

The light on the reset button keep flashing saying that it is locked out how can it be unlocked

Blower trouble with gas furnace [ 6 Answers ]

The blower on my gas furnace doesn't always start. The thermostat is fine and the blower spins freely. The furnace lights off fine but sometimes the blower doesn't want to start. I should mention it is a direct drive blower. (no belt). Do I need a new motor. Or could it be a faulty switch or relay...

No heat, blower runs constantly, carrier gas furnace [ 7 Answers ]

This am we I got up the blower on my carrier series 100 gas furnace (approx 10 years old)was running and blowing out cold air. Even with the thermostat turned to off the blower runs constantly. The only way to stop the blower from running is to turn the switch on the side of the furnace to off or...


View more questions Search