    Furnace over-run
    Furnace heats and runs for an appropriate amount of time, say 5-10 minutes depending on weather. After this running phase, approximately 2 minutes later, the furnace blower (no gas ignition) turns on and runs for 30-45 seconds. It does this for every cycle.

    I had a service call and they checked the furnace but found no problem. They did manipulate the furnace to run and when they stopped it, it did not over-run.

    The furnace is 18 years old and this started last year. The thermostat has been replaced to no avail.
    ma0641's Avatar
    ma0641 Posts: 15,675, Reputation: 1012
    Uber Member
     
    #2

    Jan 8, 2011, 11:15 AM
    Sounds like your fan ON temperature is set too low or the fan OFF temperature is set too high. One way or another, residual heat from the exchanger is making the fan turn on. I'd set the fan ON temperature a bit higher and the fan OFF a bit lower. The fan switch is located inside the heater on the exchanger casing.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

How often should oil furnace run? [ 0 Answers ]

I have a Lennox X15 heat pump and due to the lower electrical cost on my dual energy plan, it appears to be saving me a fair bit of money, while also providing A/C in the summer months. However, this year, I feel that my oil furnace is kicking in more often than it did last winter (about once /...

Furnace won't run. [ 1 Answers ]

My furnace won't run unless I go down and lift door and put it back on again. After doing this it will lite and run for one cycle and that is it, I have had it cleaned, and was told it was fixed, but still doing the same thing. I think it has something to do with the door switch. Any help please....

Furnace Blower Motor Runs Constantly & Furnace or AC Won't Run [ 2 Answers ]

I have an Armstrong forced air (induced draft) natural gas furnace with central AC (made around 1990 -- Model: EG6H80DC14-1, Serial: A18315MNA). I had a problem at the end of the heating season where the blower motor would run continuously (even when the thermostat is turned to "off"). I thought...

Run furnace all day? [ 1 Answers ]

Hi, I just installed a high efficiency gas furnace (Carrier Infinity 96) with variable speed blower motor. To save energy costs should I allow the system to run continuously at low speeds during the day when I am at work or use the timer to turn it off in the morning and on in the late...


View more questions Search