    Kitchen/Laundry venting question
    My kitchen sink and washer (in the basement) sewer drains connect in a closed system to a sewer pipe 50 feet away from the main stack (I think it is a second sewer line because it doesn't seem to enter the main stack). It is not vented and the kitchen sink bubbles and gurgles when the washer empties. In addition, when the sink drains I have concerns that it might empty into the washer if a large amount of water goes down the drain. I want to install a dishwasher (not present now) as well as a garbage disposal. I do not want to do this before I add a vent to this line. Do I have to run the vent up through the three floors of the house to the roof or can it be vented through the exterior wall?
    Milo Dolezal's Avatar
    Milo Dolezal Posts: 7,192, Reputation: 523
    Plumbing Expert
     
    #2

    Jun 9, 2010, 09:28 AM
    Hello Jminarcik,

    You could install vent through the wall to the exterior and then run it surface-mounted all the way above the roof. Exposed section of vent should be Cast Iron. If plastic (ABS or PVC) than it would have to be boxed in.

    In my area of operation, you cannot terminate vent horizontally on exterior wall.

    Better option is to install so called AAV vent ( Air Admittance Vent ) under the kitchen sink. This vent is legal in some states and not legal in others. Call your Inspector and ask him. AAV installs right after kitchen trap and admits air during sink draining eliminating gurgling sounds. See the pic...

    I suggest that you install AAV vent on existing washing machine drain as well...

    Hope that will answer your question. Good luck with your project. Milo
    Attached Images
     
    jminarcik's Avatar
    jminarcik Posts: 2, Reputation: 1
    New Member
     
    #3

    Jun 9, 2010, 10:53 AM

    Thanks Milo. According to current code they are legal to install. Is there any concern installing one after a garbage disposal?

    As for installing one on the washer drain, my thought would be it might leak/foul if the kitchen sink were to back up since the vent would be lower then the water line of the kitchen sink. Is this a concern?

    Thanks again!
    Milo Dolezal's Avatar
    Milo Dolezal Posts: 7,192, Reputation: 523
    Plumbing Expert
     
    #4

    Jun 9, 2010, 11:01 AM

    That should not be a concern. Here is why: Dishwasher drains to Garbage Disposer and Garbage Disposer drains into Branch T before P-trap. AAV is then installed after P-trap.

    AAV vent, installed lower then Kitchen Sink should not leak since it is One-Way device. It is like a snorkel: it allows air IN but seals against Odor and / or water backing out.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Venting laundry sink [ 1 Answers ]

I have tried to draw my situation. I need to vent a laundry sink (which is is the basement) an I do not have the option of running a new vent to the attic. So must I use an AAV, or can I vent into the main stack even though I am downstream from a toilet? Doesn't seem like I can go in to the main...

Kitchen Laundry [ 1 Answers ]

Hi there We are trying to install our laundry in the kitchen. Can we tie the plumbing into the kitchen sink (drain and pipes) if there is a dishwasher attached as well... is this too much in one drain down?? This house is a mess and we could really use Holmes on Homes. To run the plumbing from...

Laundry Tub Venting [ 1 Answers ]

I live in Wichita, KS, and have a basement with laundry room facilities in it. With that, venting is critical. The short part of my question is: I want to move my washer to the right about four to five feet, which means relocating the drain and venting pipes. One problem is that the pipes cross...

Converting old kitchen to laundry room [ 5 Answers ]

Hi all, My friend and I are converting an old apartment kitchen into a laundry room. What we have to work with is the following (surveying the wall from left to right): a gas stub-out (we'll worry about the dryer later); a few feet to the right there are the bodies of two gate (or globe?) valves...

Venting basement laundry [ 2 Answers ]

I'm moving my basement laundry, and the kitchen sink/dishwasher above (they share a drain line). I don't think the current setup is correct, and I would like to try to make it correct when I move the drain. Currently... My house was built in the 1920s. It has a single vent stack(?) that...


View more questions Search