    Drain pressure
    I live on the 1st floor and when the unit above me uses their kitchen sink I hear the water running down the pipes, then it appears that water from my water trap backs up to just about the top of the drain. It sort of spits, and them I get a bad smell. We had the plumber clean my drain to the main drain pipe so it does not appear that the problem is caused by a blockage. I'm guessing that either A) the water from the unit above is creating pressure and that it is pushing the air back out through the water trap back to the sink drain. Note not much water actually comes out of the drain. Or B) the water passing through the main pipe is creating a vacum that springs back with pressure and pushes the water trap back up to the sink drain. I'd like to know what the cause is. Also I did some research and found the Air Admittance Valves (AAVs). Would this solve my problem? Any help would be appreciated. Thank you.
    cdad's Avatar
    cdad Posts: 12,700, Reputation: 1438
    Internet Research Expert
     
    #2

    May 7, 2010, 05:13 PM

    The drain pipe should vent and its usually located at roof level. If the blockage is there is could caus the symptoms your describing.
    ballengerb1's Avatar
    ballengerb1 Posts: 27,378, Reputation: 2280
    Home Repair & Remodeling Expert
     
    #3

    May 7, 2010, 07:41 PM

    Adding an AAV is not a good fix for your situation but rodding from the roof is. Use enough rod to reach roof top to basement plus 20'. If these are rental units do not do the work yourself or hire out, complain to management company
    tlee404's Avatar
    tlee404 Posts: 2, Reputation: 1
    New Member
     
    #4

    May 15, 2010, 01:30 AM
    Update: I described my problem to a plumber. He said that each unit has a separate connection to a central vent. Therefore he would have to tear into the wall to get at the pipe connecting my unit to the main vent.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Septic sys, drain field, air pressure. [ 1 Answers ]

Very old septic system, has worked well for years. CLeaned every 2-3 years. Tree fell across drain field feeder line. Since that time, I think, the septic fills quicker requiring emptying. At last emptying, we put a hole into the drain field line discovering it had air pressure and was dry...

Water Pressure Test for New Drain Pipe [ 4 Answers ]

Pressure water test I am instaling the drain pipe for a new sink, I have the pass a city inspection wich requiere a water pressure test. I understand that I need a 5 feet pipe over ground. But I need more to do it. Could any one give me more detail? Marino

Pressure & Temperature Valve Plumbing to Drain [ 4 Answers ]

What are my options to plumb a T&P valve to the main building drain, including providing an air gap and P trap. Particularly, what air gap devices are available?

Drain with back pressure [ 6 Answers ]

I have a conventional sceptic system with two tanks - each serving one wing of my house. My laundry room deep sink drain has pressure on it, enough to raise the water level in the sink about 10". This happens even when there is no water running down any drains connected to this wing - I even...

How do I drain my pressure tank [ 1 Answers ]

I need to replace the faucet cartridges in my shower because it drips when it is shut off. The problem is that there is no shut off valve for the shower. Two different plumbers have told me that they would shut off the pump at the breaker switch and drain the pressure tank. By process of...


View more questions Search