    Is it OK to run #12 Romex to a ceiling fan?
    I installed a ceiling fan using #12 Romex (didn't have any #14 handy), any concerns or issues with using #12 vs. #14?
    carpenter-t's Avatar
    carpenter-t Posts: 88, Reputation: 19
    Junior Member
     
    #2

    Feb 7, 2010, 12:36 PM

    12 is actually better.
    stanfortyman's Avatar
    stanfortyman Posts: 5,598, Reputation: 279
    Electrical & Lighting Expert
     
    #3

    Feb 7, 2010, 01:04 PM
    Quote Originally Posted by carpenter-t View Post
    12 is actually better.
    WHY??
    If the circuit is #14 already then #12 is not at all better. It is legal, but is also harder to work with and will fill boxes quicker than #14.
    carpenter-t's Avatar
    carpenter-t Posts: 88, Reputation: 19
    Junior Member
     
    #4

    Feb 7, 2010, 01:53 PM

    I guess if he's coming off and existing box with#14 its not.but most of the electricians that I know personally say they use #12 coming of the panel unless money is an issue
    FLnative's Avatar
    FLnative Posts: 2, Reputation: 1
    New Member
     
    #5

    Feb 7, 2010, 02:00 PM
    Quote Originally Posted by stanfortyman View Post
    WHY???
    If the circuit is #14 already then #12 is not at all better. It is legal, but is also harder to work with and will fill boxes quicker than #14.
    Thanks for the reply. What do you mean by fill the box quicker than with a #14. Are there any concerns or hazards? I have the opportunity to go back and use #14, wanting to know if it makes sense or not.
    carpenter-t's Avatar
    carpenter-t Posts: 88, Reputation: 19
    Junior Member
     
    #6

    Feb 7, 2010, 02:03 PM

    I think I will not give advise in this area any more seeing I'm not an electrician and would not want anyone to get hurt or burn down their house.I'll stick to carpentry,gambling,booze and woman.well maybe not woman that could be worse trouble than burning down a house.
    carpenter-t's Avatar
    carpenter-t Posts: 88, Reputation: 19
    Junior Member
     
    #7

    Feb 7, 2010, 02:06 PM
    #12 is thicker so its harder to bend and it takes up more room.
    stanfortyman's Avatar
    stanfortyman Posts: 5,598, Reputation: 279
    Electrical & Lighting Expert
     
    #8

    Feb 7, 2010, 02:21 PM
    Quote Originally Posted by carpenter-t View Post
    but most of the electricians that i know personally say they use #12 coming of the panel unless money is an issue
    This is a popular mentality. The old "bigger is always better" mentality. I think it is more of a "macho" way of thinking. "Hey, I only use the BIG stuff."
    I personally do not subscribe to this.

    There are several reasons not to use #12 for many circuits in a house.
    - Box fill
    - Ease of use with dimmers
    - Ease of use with 3-way and 4-way switching
    - Ease of use in multi-gang boxes
    - Wiring in recessed lighting boxes
    - Wiring in bath vent fan boxes

    Others will say it is a money thing for using #14 for some circuits. I will say this is rarely the case.
    mcad's Avatar
    mcad Posts: 12, Reputation: 3
    New Member
     
    #9

    Feb 7, 2010, 04:28 PM
    I agree with Stan, most of the circuits I run these days seem to be 20 amp, so when I get the chance to work with #14 I take it! Although I do know a lot of electricians that just say it is easier to keep only one type of wire on the van. To each his own I guess.
    stanfortyman's Avatar
    stanfortyman Posts: 5,598, Reputation: 279
    Electrical & Lighting Expert
     
    #10

    Feb 7, 2010, 04:36 PM
    Quote Originally Posted by mcad View Post
    Although I do know alot of electricians that just say it is easier to keep only one type of wire on the van.
    These are the guys driving a Dodge Caravan or Subaru wagon. :rolleyes:
    mcad's Avatar
    mcad Posts: 12, Reputation: 3
    New Member
     
    #11

    Feb 7, 2010, 05:32 PM
    Quote Originally Posted by stanfortyman View Post
    These are the guys driving a Dodge Caravan or Subaru wagon. :rolleyes:
    Yeah especially here in Pennsylvania where you don't even need a license! Lord help us!
    ceilingfanrepair's Avatar
    ceilingfanrepair Posts: 5,733, Reputation: 109
    Uber Member
     
    #12

    Feb 10, 2010, 12:27 AM
    Quote Originally Posted by stanfortyman View Post
    WHY???
    If the circuit is #14 already then #12 is not at all better. It is legal, but is also harder to work with and will fill boxes quicker than #14.
    Well, if you ever wanted to upgrade to a 20 amp circuit, you'd already have 12.
    stanfortyman's Avatar
    stanfortyman Posts: 5,598, Reputation: 279
    Electrical & Lighting Expert
     
    #13

    Feb 10, 2010, 06:06 AM
    Quote Originally Posted by ceilingfanrepair View Post
    Well, if you ever wanted to upgrade to a 20 amp circuit, you'd already have 12.
    Then use a 20A breaker from the start. :cool:
    IMO this is not an "upgrade". It is incorrectly installing a breaker that is too small.
    Why throw away 5a worth of circuit from the get-go? :confused:

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Wiring a ceiling fan in middle of run, outlet at end of run [ 5 Answers ]

I am wiring a bedroom ceiling fan and just needed someone to help me figure out part of the wiring I'm not sure about. The goal is to have a 2 gang switch control the light and the fan separately. The switch is at the beginning of the run, then the ceiling fan, and then I also have an "always...

Ceiling Fan Won't Run [ 4 Answers ]

I have an older, very well built ceiling fan made by Harbor Breeze, which I understand is a Lowe's exclusive, but because it is older, cannot get any info on repairs from Lowe's or anywhere else. The problem is, the fan will sometimes run, but then the next time will not come on at all. We've...

Ceiling Fan Doesn't Run with Blades on [ 13 Answers ]

The blades on my ceiling fan were loose. When I tightened them, the fan would not turn. I tried loosening them again to their previous position, but no luck. When I remove the blades, the assemble runs at full speed. When the blades are reattached, it does not run or runs very slowly. I have...

Why will the ceiling fan only run in one speed now [ 3 Answers ]

Harbor Breeze ceiling fan will only run in one slow speed now. House is not even two years old. Any suggestions other than to toss it? Thanks Jeff

Cost to run a ceiling fan [ 2 Answers ]

How much does it cost to run a ceiling fan at low speed?


View more questions Search