    Gas furnace won't stay running!
    Hello, I have a Tempstar gas furnace model# NDN6050FBA1, It runs for 1-2 minutes then shuts off. I can hear the fan turn on, gas ignite, and then the blower motor. It doesn't run long enough to heat up and of coarse we are experiencing freezing temps. I wonder if my thermostat is going bad? Any suggestions would be greatly appreciated.

    Thanks, Kevin
    kevinj1w's Avatar
    kevinj1w Posts: 6, Reputation: 1
    New Member
     
    #2

    Dec 21, 2008, 06:26 AM

    Forgot to mention everything is clean, had the furnace serviced last spring.
    KC13's Avatar
    KC13 Posts: 2,556, Reputation: 99
    Ultra Member
     
    #3

    Dec 21, 2008, 08:13 AM

    If you can see the burner area, how long is flame present before shutting down?
    kevinj1w's Avatar
    kevinj1w Posts: 6, Reputation: 1
    New Member
     
    #4

    Dec 21, 2008, 08:33 AM

    Its present for about 1 min or more but no more than 2 min.
    kevinj1w's Avatar
    kevinj1w Posts: 6, Reputation: 1
    New Member
     
    #5

    Dec 21, 2008, 08:48 AM
    I started messing with the thermostat to figure out which wire do what. Now the furnace is putting out some heat. Maybe my thermostat ( electronic Honeywell) is starting to go.
    KC13's Avatar
    KC13 Posts: 2,556, Reputation: 99
    Ultra Member
     
    #6

    Dec 21, 2008, 09:40 AM

    Try this: turn off power to furnace, disconnect "R" and "W" wires from thermostat, and connect them together. Now power up furnace and see how it runs.
    kevinj1w's Avatar
    kevinj1w Posts: 6, Reputation: 1
    New Member
     
    #7

    Dec 21, 2008, 06:57 PM

    Thanks kc13, After my last post the furnace started to work and heated the house. If it happens again I will try this.
    Thanks again, Kevin
    MarkwithaK's Avatar
    MarkwithaK Posts: 955, Reputation: 107
    Senior Member
     
    #8

    Dec 21, 2008, 07:21 PM
    Quote Originally Posted by kevinj1w View Post
    Forgot to mention everything is clean, had the furnace serviced last spring.
    I'm going to almost bet that your flame sensor is dirty and causing an intermittent problem. Just because it was cleaned last spring doesn't mean that they cleaned the FS. A spring inspection/cleaning is usually more targeted at A/C operation. I usually recommend a clean and check 2 times a year. Once in late spring for A/C season and then again in early fall for heat season.
    kevinj1w's Avatar
    kevinj1w Posts: 6, Reputation: 1
    New Member
     
    #9

    Dec 22, 2008, 08:06 AM

    Thanks Mark, as of know everything is working like it should and I'll take your advice and clean the flame sensor.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

16 hp b&s won't stay running [ 2 Answers ]

Hi, I have an older simplicity tracotr with a 16 hp briggs and stratton engine. When it starts it runs OK at low throttle or just to put around, when you increase throttle and let off the clutch the engine dies. This also happens when I engage the blades. I throttle up and engage the blades, and as...

Why won't my snowblower stay running? [ 4 Answers ]

I have a five horse power snowblower and the only way I can start it is using the electric start on it. When it is started it will stop running when I go to blow the snow. The only way I can blow snow is if I have it in first gear and I have to keep stopping so it will catch up on blowing the...

Old B&S won't stay running [ 7 Answers ]

I need help. I have this old B&S motor and it run if I put gas straight into the spark plug and air filter but will run for 3 seconds then die. Anyone help me?:confused:

Kerosene furnace won't stay running unless . [ 1 Answers ]

I have a kerosene furnace that needs to be bled every time in order for it to run what could be the problem (I have 1/4 tank of fuel ):confused:

Won't stay running [ 14 Answers ]

I have a 91 crx it sat up since may and I just put a d15b vtec in this past weekend. I sat the engine in and hooked up all appropriate connectors with the exception of two wires that is close to the intake manifold (yellow w/ green and a black) I have no clue where they go all I know is if you...


View more questions Search