    Gas Heater Thermostat
    I recently bought a farm house with basement. All the water pipes are in the basement. I'm thinking of putting a 2nd thermostat for the heater in the basement and set it at 35 degrees to keep pipes from freezing when no one is at the house. I haven't been able to find one. Most don't go below 40 or 45. Any ideas?
    21boat's Avatar
    21boat Posts: 2,441, Reputation: 212
    Ultra Member
     
    #2

    Dec 18, 2008, 05:45 PM

    Well 35 is to close to 32 or 31 freezing. I would use the ones you found that goes down to 40. What if there is a cold snap and its 35 at your stat and the pipe on the other side of the basement is 28? There's good reason of 40 and not 35 stats You have a farm house and how well is the insulation and you just bought it. I would be Leary at setting it at even 40. I'm in the farm capital of the U.S. Lanc pa. Amishville. I know how scary the farm houses are in insulation most are nothing but solid brick walls or stone walls Stick with the 40 please. I know you want to save money but at what cost if a pipe freezes and burst and thousands of dollars of damage. This is not to be messed with be safe 45 min. and test it before you leave. See how much degrees difference from rooms to rooms. I know that's not the answer your looking for but all I see here is trouble or Major damage do to frozen pipes. Hope I stilled helped Happy Holidays!
    MarkwithaK's Avatar
    MarkwithaK Posts: 955, Reputation: 107
    Senior Member
     
    #3

    Dec 18, 2008, 07:44 PM

    You cannot use a secondary stat in line with your current stat.
    KC13's Avatar
    KC13 Posts: 2,556, Reputation: 99
    Ultra Member
     
    #4

    Dec 18, 2008, 07:55 PM

    A mouse trap by any other name... maybe just set your current thermostat to 45-50 and fuggetaboutit...

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Thermostat set but heater won't lite [ 2 Answers ]

We have programmed the thermostat and can hear the fan running but no flame appears, this is an electric ignition Amana furnace approx 15 yrs old. There is gas, you can smell it, and the furnace seems to go through the cycles but still no heat. The batteries have been changed in the thermostat and...

Baseboard heater thermostat issue [ 7 Answers ]

I have a marley heater 4 foot. On the heater is a double pole thermostat. There's 2 black wires and 2 red wires. 1 of the black wires reads cycle, the other black wire reads off. 1 of the red wires reads l1 and the other red wire reads l2. The power source coming to the heater is 2 black wires @...

Old heater/new thermostat [ 1 Answers ]

I need to know where r,w,c are on my heater

Central heater comes on when thermostat is on OFF [ 1 Answers ]

My 2nd floor heater has came on 3 times when the thermostat is on OFF. Only thing I changed was the filter 2 weeks ago. Battery is fine. This problem occurred 2 years ago in the summer time and I had the dualzone circuit replaced. Now it's happening again. Basic info: I have dual...

Water Heater electric thermostat [ 1 Answers ]

I have a two year old water heater with an electric thermostat attched to the front of the water heater. To change the temp you have to push both the aarows (one blue one red) and hold for about 3 seconds then the LED lights appear and you can change the setting. What has been happening since I...


View more questions Search