    6/3 to stove plus ground
    I'm wiring a stove outlet , have on hand enough 6/3 ,(red, black, white) to do so except that I see that later NEC requires separate ground wire. This cable does not have it , but could I add ground wire from stove receptacle back to closest outlet box that grounds back to service panel?
    561packrat's Avatar
    561packrat Posts: 80, Reputation: 1
    Junior Member
     
    #2

    Sep 17, 2008, 12:12 PM
    Quote Originally Posted by 561packrat
    I'm wiring a stove outlet , have on hand enough 6/3 ,(red, black, white) to do so except that I see that later NEC requires separate ground wire. This cable does not have it , but could i add ground wire from stove receptacle back to closest outlet box that grounds back to service panel?
    still wondering,let me know please
    stanfortyman's Avatar
    stanfortyman Posts: 5,598, Reputation: 279
    Electrical & Lighting Expert
     
    #3

    Sep 18, 2008, 03:05 PM
    Duplicate thread
    https://www.askmehelpdesk.com/electr...ml#post1281560

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

England Stove Works pellet stove blower speed [ 1 Answers ]

Greetings, I have an England Stove Works 25-PDVC/55-SHP10 pellet stove. We've had it for almost four years with no problems. I clean it out and grease the augers every fall before running it for the winter season. It has recently started having a problem with the blower speed. We start it...

Leveling the ground with mulch for above ground pool [ 3 Answers ]

I was wondering if I could use mulch to level the ground for my above ground pool. I was told not to use sand, and I have a hard time digging.

Do you install a 120v 15 or 20 amp receptacle ground up or ground down? [ 15 Answers ]

Does the code have any stipulations on ground up or ground down? If so Prove it. An I am not talking about local ordinances nor the authority having jurisdiction. Simply the NEC.

England Stove Works pellet stove [ 0 Answers ]

I was wondering if anyone had a problem with their blower fan making a "whaling" sound? If so, what did you do? Model #25-PDVC/55-SHP10 Also, did you ever have a build up of unburned pellets? I have heard that this could be the result of type of pellets used. Hardwood vs. hardwood blend

Open ground when neutral not touching ground [ 3 Answers ]

Hi, I was moving around a room and noticed my wife wanted her desk elsewhere. I decided to, since she would have her computer on it, check the outlet she would be moving to. It seemed old so I changed it. I noticed before I changed it that with my GFCI tester, all sockets on this circuit were...


View more questions Search