It was definitely human waste. I could tell by the odor and visual. Our builder said that the line is connected to the rest of the plumbing for whatever that is worth.
If sewage managed to make it's way into the condensate line, then the problem is twofold:
1) The condensate drains should have been plumbed to a trapped indirect drain or floor drain with a minimum of a 1" air break between the outlet of the condensate drain and the inlet of the indirect receptor/floor drain -- Condensate drain lines should never be piped directly into a waste line.
2) If sewage managed to enter the condensate drain, then it could only have done so if a drain line had backed-up.