  • Jun 30, 2010, 06:57 PM
    roncarl
    For an Above Ground Pool, can I run UF-b 12-2 wire in Schedule 40 Conduit?
    Im running underground wiring from my house about 8 feet to an 18 foot round 48 inches deep to pool pump using GFCI on outside of house and Twist lock outlet 6 feet from pool.
    Can I use UF wire run through schedule 40 conduit or do I need to use THWN single conductors through conduit?
  • Jun 30, 2010, 07:11 PM
    Stratmando

    It needs to be individual conductors, Romex in conduit will not get rid of the heat.
    Why Twistlock? It may get tripped on and expose conductors.
  • Jun 30, 2010, 08:34 PM
    roncarl
    Comment on Stratmando's post
    The Town requires twist-lock for filter.