  • Oct 23, 2008, 02:15 PM
    FRANKKINCAID
    Bryant Furnace Model 100-394U Won't Light Up
    My bryant furnace model 100-394u won't light up.the gas is on,the pilot is on but it still won't light. Last year I put a new hunter thermostat and it worked all winter but this year it won't start any advise
  • Oct 23, 2008, 04:14 PM
    wmproop

    Wow,, if you got a year out of a hunter tstat,consider yourself lucky, they are junk
  • Oct 23, 2008, 06:16 PM
    T-Top
    Check to see if you have 24v at the gas valve(when the thermostat is calling for heat). If you don't have 24v, jump from R to W on the low voltage. If no flame or 24v on the gas valve after that make sure you have a 115v to power the furnace and transformer. Make sure you put the gas valve back to on after lighting the pilot. This unit has to be around 30 years old.