I have an evcon furnace model # dgat070bdc and it will not ignite. My gas is full an the blower kicks in when heat is called for but I get no heat. I have replaced the hot surface ignitor an the ignition control. What is the problem?
I have an evcon furnace model # dgat070bdc and it will not ignite. My gas is full an the blower kicks in when heat is called for but I get no heat. I have replaced the hot surface ignitor an the ignition control. What is the problem?
Does the ignitor glow? Does the vent motor run? And can you hear the gas valve click to send in the gas??
No it doesn't glow. An yes the motors are blowing, the vent motor is the smaller one rite? An I don't hear any clicking.
Sometimes it's the small things, the circuit breaker on top of the furnace was tripped, just give me the big dummy award
If that was the heat overload you reset you may still have a problem. Usually they have a small red button in the center to push in. Look for dirty air filter. Closed registers, restricted return air. If this is in a mobile home you cannot close off the registers in the rooms you are not using.