  • Jul 3, 2009, 02:45 AM
    ssaha
    How can I calculate maximum demand load from connected load in KW
    Hi I am ssaha, I want to ask, how can I calculate maximum demand load from connected load? Suppose in a shopping complex cannected load is 5000 KW. Only connected load is known but other component like demand factor not specified. In that case how can I calculate maximum demand load? Please help me.
  • Jul 3, 2009, 04:32 AM
    tkrussell
    You need to calculate the total loads that will be on at one time.

    If your located in USA, or for reference, you can begin reviewing Article 220 of the
    NFPA 70: National Electrical CodeŽ

    Table 220.3(A), which lists watts per square foot for general lighting in various types of facilities, may help.

    Since you already have connected load, you already have the actual total lighting load. Heating and cooling load can be added, making assumptions of what will be total load based on need of either.Next add large intermittent loads, such as elevators, trash compactors, dishwasher booster heaters.

    Generally, another way of thinking, is to add all continuous loads, and then add a judgment of non-continuous loads. Your total connected load will have these continuous loads, and you need to add what the total non-continuous loads will be.

    Don't forget to consider exterior lighting and signage only used at night.

    Here are a few references to get you started:
    http://www.nfpa.org/assets/files/PDF...sues072704.pdf

    Demand load - Wikipedia, the free encyclopedia

    Commercial Load Calculations
  • Apr 1, 2012, 11:06 PM
    azeezp
    Kw/.85
  • May 16, 2012, 02:36 AM
    sdchaudhari7
    I want to know what is total connected load for 3 phase commertial consumer. Lt ii(c)
    Service rovider reliance energy , mumbai maharashtra

    max. demand is 31.18 kva,
    Connected demand-50 kva
    Units consumed- 5931
    Bill amount- rs 88109.15
    Billing demand is 20.27kva 65% of max demand during 6 - 22 hrs

    Demand fix charge- rs 3040.05
    Energy charge rs75169.90
    Energy charged rs 10.91/unit