    kpierre's Avatar
    kpierre Posts: 3, Reputation: 1
    New Member
     
    #1

    Jan 21, 2008, 05:32 PM
    When adding a GFCI disconnect for hottub, should I replace GFCI in service panel?
    I have a hottub now but without a disconnect. Its simply a 6/3-50 amp wire that runs from the hottub to a 50amp GFCI inside the house main service panel. I want to install a disconnect 5-10 feet from the hottub. I bought a disconnect box that already has a GFCI inside of it.
    Should I have bought one that does not have a breaker inside?
    If I use this one, should I replace the GFCI in the main service panel with a regualr breaker? If not, will 2 GFCI's on one circuit cause it to have false trips?
    ballengerb1's Avatar
    ballengerb1 Posts: 27,378, Reputation: 2280
    Home Repair & Remodeling Expert
     
    #2

    Jan 22, 2008, 12:32 PM
    Either get a disconnect without a GCFI built into it or pull the GFCI from the main panel. You do not want 2 on the same circuit.
    kpierre's Avatar
    kpierre Posts: 3, Reputation: 1
    New Member
     
    #3

    Jan 22, 2008, 12:45 PM
    Quote Originally Posted by ballengerb1
    Either get a disconnect without a GCFI built into it or pull the GFCI from the main panel. You do not want 2 on the same circuit.
    Because?
    -If it's a waste of money to have both, I already have both and will cost more to eliminate one of them.
    -If because it will not work properly, then I have no choice to spend more money
    KISS's Avatar
    KISS Posts: 12,510, Reputation: 839
    Uber Member
     
    #4

    Jan 22, 2008, 12:54 PM
    It will work and it's probably legal. Portable Hair dryers are sometimes supplied with a GFCI on the cord. They are plugged into GFCI outlets sometimes.

    What will happen is depending on the tolerences of the particular devices employed, one may trip faster than the other or both may trip and it may not be predictable, so if you have a trip, you may have to check both devices. It may mean that one particular GFCI may trip first most of the time.
    kpierre's Avatar
    kpierre Posts: 3, Reputation: 1
    New Member
     
    #5

    Jan 22, 2008, 01:02 PM
    Quote Originally Posted by KeepItSimpleStupid
    It will work and it's probably legal. Portable Hair dryers are sometimes supplied with a GFCI on the cord. They are plugged into GFCI outlets sometimes.

    What will happen is depending on the tolerences of the particular devices employed, one may trip faster than the other or both may trip and it may not be predictable, so if you have a trip, you may have to check both devices. It may mean that one particular GFCI may trip first most of the time.
    Thanks - greatly appreciated

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Adding New Service Panel [ 1 Answers ]

I have maxed out my existing Service Panel. I want to add a small additional panel approximately 30 feet away in more convenient, permanently unfinished portion of my basement. I have been told in need to run 6 gauge wire for this from my existing panel. Does anyone know if I need to run this...

Replace service panel [ 7 Answers ]

I have 100amp service panel for my entire house. I am wanting to upgrade to 200amp and have bought a new service panel. I am comfortable working with this type of project but the only thing I am unsure of and cannot get a straight answer on is if I can just install the new panel, removing the...

Adding GFCI Breaker to Existing Subpanel [ 4 Answers ]

I want to add a GFCI breaker to an existing sub panel (used to power a hot tub) so I can have a protected outlet on my patio. However, I'm confused as to how to wire in to the existing wiring. The existing sub panel has a double pole 50A breaker with 2 hot wires (red and black) and a neutral...

Gfci spa panel tripping [ 4 Answers ]

I just installed a spa with 4 wires. The house is old and while the neutral & ground bus bars are separate in the spa panel, they are all on the same bar in the main panel. Do I need to install a ground rod by the spa panel to keep the gfci from tripping? (instead of running the ground back to the...