    roncarl's Avatar
    roncarl Posts: 3, Reputation: 1
    New Member
     
    #1

    Jun 30, 2010, 06:57 PM
    For an Above Ground Pool, can I run UF-b 12-2 wire in Schedule 40 Conduit?
    Im running underground wiring from my house about 8 feet to an 18 foot round 48 inches deep to pool pump using GFCI on outside of house and Twist lock outlet 6 feet from pool.
    Can I use UF wire run through schedule 40 conduit or do I need to use THWN single conductors through conduit?
    Stratmando's Avatar
    Stratmando Posts: 11,188, Reputation: 508
    Uber Member
     
    #2

    Jun 30, 2010, 07:11 PM

    It needs to be individual conductors, Romex in conduit will not get rid of the heat.
    Why Twistlock? It may get tripped on and expose conductors.
    roncarl's Avatar
    roncarl Posts: 3, Reputation: 1
    New Member
     
    #3

    Jun 30, 2010, 08:34 PM
    Comment on Stratmando's post
    The Town requires twist-lock for filter.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

3 wire plus metal conduit as a ground for a range [ 4 Answers ]

I am installing a new range. I have a three wires coming out of a metal conduit which is properly connected to a 60 amp breaker. I have a three wire cord and a grounded surface mounted outlet. I assume that the ground will connect through the metal conduit. THis will ground the outlet. How do I...

Correct method to RUN copper ground wire to ground a 200 amp electrical circuit box? [ 0 Answers ]

Is a 3-wire copper ground or a solid copper wire required to ground a 200 amp electrical box? Is this wireing correct: A 3-wire copper ground wire in a conduit run from the electrical panel to the copper rod in the ground then to the cold water; AND THEN IN THE GARAGE the naked 3-wire...

Disposal replacement - no ground wire in conduit? [ 2 Answers ]

I am replacing my disposal, and when I disconnected the wiring, I see there is one white and one reddish wire - no ground. Is this even safe? I am not sure I should continue, but it's really inconvenient not too... as you can imagine!

Ground wire in separate conduit. [ 1 Answers ]

Is it required by code to run the ground wire in the same conduit as the hot and nuetral conductors?

Can you use Metal Conduit as ground to convert 2 wire to 3 wire? [ 3 Answers ]

I need to convert an old cinder block house from 2 wire outlets to 3 wire by adding a ground to all outlets. Since the entire house is cinder block, all the circuits from the basement breaker box are in flexible metal conduit and metal outlet boxes... Is it possible to use the metal conduit...


View more questions Search