    Water filteration system
    I am re-installing an undersink water filteration system. The supply line for the filter is a 1/4" flexible plastic tubing.
    Also, I don't want the filteration constantly supplied with water. We should be able to turn the water supply on and off to the filteration system.
    The current cold water valve and supply line is 3/8".
    What sort of valves and fittings do I need for this project. I know there will be some sort of T-connector involved and there will be some kind of valve to turn the supply on/off to the filteration system.


    Any help you can provide with the links to the plumbing supplies on homedepot/lowes website will be much appreciated.


    Thank you.
    speedball1's Avatar
    speedball1 Posts: 29,301, Reputation: 1939
    Eternal Plumber
     
    #2

    Sep 16, 2014, 06:21 AM
    Do have a opening un your si8ng to install a chrome water tap? If not do you have a stainless steel sink? What you want to do is doable but you will need tools and some plumbing skills, Still want to proceed? Back to you, Tom
    hkstroud's Avatar
    hkstroud Posts: 11,929, Reputation: 899
    Home Improvement & Construction Expert
     
    #3

    Sep 16, 2014, 06:48 AM
    What type of piping do you have, copper of CPVC?

    Does piping come through the back of the cabinet or the floor?
    Do you have enough room between the existing stop valve and the back or the floor to install a tee fitting?
    The supply line for the filter is a 1/4" flexible plastic tubing
    Is that 1/4" inside diameter or outside diameter? A 1/4" inside diameter should be 3/8" outside diameter.
    aamirghanchi's Avatar
    aamirghanchi Posts: 4, Reputation: 1
    New Member
     
    #4

    Sep 16, 2014, 07:28 AM
    They are metal pipes, but not copper coming out of the floor.
    Yes I have enough room all around.
    1/4" is outside diameter of the tubing
    hkstroud's Avatar
    hkstroud Posts: 11,929, Reputation: 899
    Home Improvement & Construction Expert
     
    #5

    Sep 17, 2014, 05:22 PM
    If pipes are metal but not copper they must be galvanized iron pipes.
    Check out this coupling at Home Depot.
    Watts 3/8 in. x 1/4 in. Brass Female Compression x Compression Adapter-LF A157 at The Home Depot

    If plastic tubing fits this adapter;

    Remove existing stop valve and install galvanized tee. Install short nipple in each out port. Install a 1/4 turn FIP (female iron pipe) to 3/8" compression stop valve on each nipple. Reconnect faucet to one valve. Put adapter on the second valve. Connect plastic tubing to adapter. You will need a brass sleeve inside plastic tubing. You may have to buy a 1/4 coupling to get that sleeve.
    aamirghanchi's Avatar
    aamirghanchi Posts: 4, Reputation: 1
    New Member
     
    #6

    Sep 18, 2014, 11:28 AM
    Probably this is exactly the part I was looking for. I am still not sure about the process you've described of adding nipples. But I will defintiely get this part and give it a try. I will let you all know.

    You guys are great!

    Thank you.

    Quote Originally Posted by hkstroud View Post
    If pipes are metal but not copper they must be galvanized iron pipes.
    Check out this coupling at Home Depot.
    Watts 3/8 in. x 1/4 in. Brass Female Compression x Compression Adapter-LF A157 at The Home Depot

    If plastic tubing fits this adapter;

    Remove existing stop valve and install galvanized tee. Install short nipple in each out port. Install a 1/4 turn FIP (female iron pipe) to 3/8" compression stop valve on each nipple. Reconnect faucet to one valve. Put adapter on the second valve. Connect plastic tubing to adapter. You will need a brass sleeve inside plastic tubing. You may have to buy a 1/4 coupling to get that sleeve.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Can shutting the main water supply off and draining the system drain water heaters [ 4 Answers ]

We have a 2 story building with multiple suites and some of the suites have water heaters. We need to shut the water down and drain the system to replace a backflow. Can this cause the water heaters to drain?? The shut off between the backflow and the building is old and we are afraid it may...

Add city water to well system for sprinkler system. [ 6 Answers ]

Hello, My sprinkler system runs off an irrigation well system with a bladder tank. The well has a 1HP Jet pump that will only pump 8 gpm @ 40-60 psi. As the system runs after 3-4 minutes the pressure will drop to 20 or so psi and the sprinkler heads start to drop. So I'm not getting enough water...

Hot water only - no cold water - soft water system [ 4 Answers ]

I have what seems like a very odd problem. I have lost water pressure to all sinks, one shower (other works fine), and the backyard hose (frontyard hose works fine). I'm very confused, but initially had a problem where some tiny gold pellets of some sort had backed up into places where we were...

How do I increase H2O pressure on well system with a water filtration system? [ 2 Answers ]

Howdy, I would like to know how I can increase my water pressure. My current system uses a well pump with a small pressure tank, and "D" control valve. It then runs through a WATERSOFT filtration tank, RAINSOFT water softner, and on the Hot water side, an AQUASTAR on demand hot water system. I...


View more questions Search