    Want to add a bath upstairs,just sink and toilet,what is the code for floor joist, ky
    Want to add a bath upstairs, just a sink and toilet, need to know the code in Kentucky for floor joist, don't know if what is there now is enough, thanks for any help
    Bljack's Avatar
    Bljack Posts: 245, Reputation: 28
    Full Member
     
    #2

    Sep 2, 2010, 12:59 PM
    Code requires certain live and dead loads be taken into considerations for the design and as long as the design meets those specifications, then it's good. It doesn't say you must have no less than 2x10's spaced 19.2" oc. Truth is your floor support can be 2x4's if the span is short enough.

    I do believe the basic half bath falls under the normal 40/10 for live and dead load considerations and that your floor structure must meet a deflection of no less than L/360 using those loads. Where you may have problems is if you are moving walls that may be supporting roof loads or if you would need to notch a joist to run your dwv lines. If notching is the case, start thinking of soffits and tray ceilings in affected rooms below.

    It's much easier to figure if what you have would meet the minimum requirements and how to amend it if needed if you posted exactly what you have right now, joist size, spacing and unsupported span as measured from supporting wall or beam below (not existing walls on the joist, but from below) vs trying to list the almost infinite possible variations of sufficient supporting structures.
    massplumber2008's Avatar
    massplumber2008 Posts: 12,832, Reputation: 1212
    Senior Plumbing Expert
     
    #3

    Sep 5, 2010, 03:58 PM

    Hi all...

    If looking to install only a toilet and a sink then you will have no issues as long as you run the toilet pipe up in the joist bay that the toilet will be in. Here, no matter the joist size, as long as you don't cut the joist you will be fine. If you can't arrange to get the pipe in the correct joist bay then you will need to let us know how large your joists are.

    In terms of the sink, if it is on the same wall as the toilet (usually is) then you may be able to install the drain line to the toilet vent above the floor... again, no joist issues there!

    Let us know more here... OK?

    Mark

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Floor joist [ 3 Answers ]

would sistering a 2x6 onto a old 2x6 be as strong as a 2x10 that should have been used? 24" on centers 14' span

Water coming up in toilet when toilet flushed or running water in sink, how to fix? [ 1 Answers ]

When I flush the toilet, take showers in my upstairs bathroom, water comes out of my downstairs shower. How can I fix this problem without calling a professional plumber?

First floor sink gurgles when upstairs sink drains [ 1 Answers ]

Greetings and thanks in advance for any help, I have an apartment building where the first floor sink gurgles when the upstairs sink drains. Would installing a studer valve in the upstairs line solve this?

Floor drain in basement floods from washer and upstairs sink [ 3 Answers ]

Why does my upstairs sink and wahser machine flood the floor drain in the basement? Every time I use the washer machine or wash the dishes in the upstairs sink it flood the floor drain in the basement, and if I am washing clothes I have to stop the water from draining into the washer sink in the...

No running COLD water upstairs in bathroom sink/bath [ 1 Answers ]

I have NO cold running water coming out of bathroom taps . The hot is running fine. This just happened all of a sudden with no cause I can think of. I have both cold and hot water downstairs running fine. The bathroom is upstairs. Can you help me Thanks .


View more questions Search