    retrofitz's Avatar
    retrofitz Posts: 2, Reputation: 1
    New Member
     
    #1

    May 21, 2005, 11:15 AM
    Unvented J Trap
    A rental property inspector recently wrote up this item that needs to be corrected: Replace the unvented J-trap under the bathroom hand lavatory.

    Background:
    I am the property owner and had this sink installed by my plumber less than a year ago. Prior to the installation the bathroom had no sink (had been that way for a hundred years, literally). I haven't had any complaints about the functionality of the drain. I talked to my plumber and he said he did not install a vent because it was within 6 feet of the stack vent that the bathtub and toilet use. He suggested he could install an inline vent if it is required and he will be looking into that.

    Questions:
    I want to see what I can learn about the terminology and requirements before I talk to the inspector. Do you think he means that the J-trap really needs to be replaced (as inspector said), or just a vent installed (as plumber suggested)? Is there such a device as a "vented J-trap"? Does an inline vent need to vent outdoors? Any code concerns about adding an inline vent?

    Thanks!

    Tom
    speedball1's Avatar
    speedball1 Posts: 29,301, Reputation: 1939
    Eternal Plumber
     
    #2

    May 21, 2005, 01:13 PM
    UOTE=retrofitz]A rental property inspector recently wrote up this item that needs to be corrected: Replace the unvented J-trap under the bathroom hand lavatory.

    Background:
    I am the property owner and had this sink installed by my plumber less than a year ago. Prior to the installation the bathroom had no sink (had been that way for a hundred years, literally). I haven't had any complaints about the functionality of the drain. I talked to my plumber and he said he did not install a vent because it was within 6 feet of the stack vent that the bathtub and toilet use. He suggested he could install an inline vent if it is required and he will be looking into that.

    Questions:
    I want to see what I can learn about the terminology and requirements before I talk to the inspector. Do you think he means that the J-trap really needs to be replaced (as inspector said), or just a vent installed (as plumber suggested)? Is there such a device as a "vented J-trap"? Does an inline vent need to vent outdoors? Any code concerns about adding an inline vent?

    Thanks!

    Tom[/QUOTE]


    Hi Tom,

    Yeah, let's talk about terminology. "P"trap not "J" trap. A "J" bend is the return bend of a "P" trap. "Inline Vent" translates to Spring Loaded Mechanical Vent in my book.
    The inspector didn't want the trap replaced, he wanted it vented and brought up to code. There's no such animal as a "vented J or P trap"
    Your plumber missed the boat on installing a vent. If there were to be no inspections he might have skated by on the 6" unvented drain but if he knew he would be inspected he should have conformed to code. Let me give you the size of the drain and acceptable distance between fixture trap and vent.
    1 1/4" drain 2 1/2' from trap to vent
    1 1/2" " 3 1/2'
    2'' '' 5'
    3" '' 6'
    If local code allows you to install a Mechanical vent that would be the simplest way to go.
    Check them out at, http://www.studor.com/homeowners.htm
    More questions? I'm as close as a click.
    Tom
    retrofitz's Avatar
    retrofitz Posts: 2, Reputation: 1
    New Member
     
    #3

    May 21, 2005, 05:12 PM
    Unvented J Trap
    Thank you for the info! :)

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

P-Trap [ 1 Answers ]

I have a townhouse with a rough-in for a shower in the basement. Would the rough-in already have a p-trap in the drain-line. Is there any way to verify if it exists? Thanks

Trap [ 1 Answers ]

I am installing a drain in my laundry room floor. What type of trap should I be using. The trap will not be getting normal use like a sink would. My fear is if I use a normal trap it will have a smell to if because lack of water running on a daily basis.

P trap [ 9 Answers ]

Hello I want to develop a basement bathroom that is diriectly under the main floor bathroom. The p trap from the main floor tub dips down about 4" below the bottom of my joists before curving back up to connect to a horizontal line that runs over to the main vented stack. I dont want to have...

Is there a trap? [ 2 Answers ]

We are finishing a full bathroom in our basement/1st floor (it's about 18" below grade). The drains were roughed, but we actually had to move the tub drain a couple of inches to accommodate the tub/shower unit we bought. With the floor busted up you can see an elbow connected to a waste line,...

Dangers of sewer pipe being unvented [ 2 Answers ]

We have recently discovered not only mold growing throughout our house but upon further investigating found the gas dryer to be unvented releasing not only moisture and carbon monoxide under the house but its also a fire hazard. After hiring a home inspecter, we found a sewer pipe that is vented...


View more questions Search