    Trying to replace a 20/40 switch with a 30/50 -no power to well pump
    Rainy day in IL today. Thought I would try and replace our 20/40 submersible well pump pressure switch with a larger 30/50. I wired it just as the 20/40 was, put the correct pressure back in the tank and the power is surging when I turn it try to turn it back on. Thought maybe the wiring wasn't big enough for a 30/50, so I put the 20/40 pressure switch back on. Still surging. Any suggestions? I will leave the 20/40 until I can get an electrician here. No water for now though.
    jlisenbe's Avatar
    jlisenbe Posts: 5,020, Reputation: 157
    Uber Member
     
    #2

    May 14, 2011, 06:51 PM

    What do you mean by "the power is surging"?

    This is how your wiring should look

    http://www.catskillhouse.us/blog/wp-...tch-wiring.jpg
    hkstroud's Avatar
    hkstroud Posts: 11,929, Reputation: 899
    Home Improvement & Construction Expert
     
    #3

    May 15, 2011, 07:07 AM

    Sounds more like a plumbing problem than an electrical problem. A 30/50 switch is not bigger than a 20/40 switch, just has different settings.

    Error was probably in pressurizing tank.

    Assuming you have a bladder type tank;

    Turn off breaker to well.
    Drain tank of all water.
    Pressurize tank to 2 lbs. below switch cut in pressure.
    That would be 18 lbs. for old switch, 28 lbs for new switch.
    Turn on breaker.

    Note: If switch is located on well pipe make sure pipe is clear and not blocked by debris. If switch has small tube from tank make sure it is clear.

    Note: To insure that all water is out of tank, pressurize with a faucet open.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Can you replace one 3 way light switch with one motion detector switch? [ 2 Answers ]

I have a series of lights in the basement that are connected to two 3 way light switches. I would like to replace one switch with a motion detector switch. Is it possible to replace only one switch with a motion detector or do I need to replace both?

Fuel pump fuse has no power at it. Could this be the ignition switch? [ 2 Answers ]

I got a 1992 Chevrolet 1500 with a 5.7l and the fuel pump isn't working. It has been sitting for about 5 years. I got a 12v test light and found out that the 20amp fuel pump fuse has no power on either side of the fuse. Could this be a ignition switch problem? The ignition switch is a little...

Taking power from existing 3 way circuit to power another switch [ 5 Answers ]

Hi, I have another question, hope its not too confusing. I have an existing 3 way switch for the lights in my stairwell. I want to change the single gang box to a 2 gang box and add another switch to power 6 new can lights. Can I disconnect the hot (black) wire and add a pigtail and feed power to...

New dimmer switch will not dim light - taking power from 3 way switch [ 2 Answers ]

New dimmer switch will not dim light - I am trying to hook up a dimmer switch in a electrical box that already contains a three way switch. I am trying to take power from the three way switch to power the new dimmer and light. The way it is hooked up now the new light works but will not dim with...


View more questions Search