    Triton showers troubleshooting
    Having a shower and turned the heat setting down to cold... on the rotatory knob... there was a dull bang and water stopped coming from the hose / head but is pouring out of a safety overflow on bottom left corner.

    Took shower apart to see if it's anything obvious, checked flow through outlet (short) pipe and through hose. All OK.

    Any ideas? Help? Advice?

    Flemmo
    tritonman's Avatar
    tritonman Posts: 3, Reputation: 1
    New Member
     
    #2

    Jul 5, 2010, 02:13 AM
    The problem you highlight would sound to be operation of the PRD - Pressure Relief Device, this is a safety valve fitted to your shower.

    Usual causes of operation is usually a blockage at the shower outlet - hose twisted / kinked or blocked shower head or perhaps a surge of pressure passing into the shower unit.

    To solve the problem you will need a new PRD which may be ordered directly from Triton Spares Dept(Tel : 0844 980 0750) and also check that there is no restriction to the outlet off the shower to ensure that the new PRD does not operate.

    Hope this info helps,

    Regards,
    TritonMan
    tritonman's Avatar
    tritonman Posts: 3, Reputation: 1
    New Member
     
    #3

    Jul 5, 2010, 02:13 AM
    The problem you highlight would sound to be operation of the PRD - Pressure Relief Device, this is a safety valve fitted to your shower.

    Usual causes of operation is usually a blockage at the shower outlet - hose twisted / kinked or blocked shower head or perhaps a surge of pressure passing into the shower unit.

    To solve the problem you will need a new PRD which may be ordered directly from Triton Spares Dept(Tel : 0844 980 0750) and also check that there is no restriction to the outlet off the shower to ensure that the new PRD does not operate.

    Hope this info helps,

    Regards,
    TritonMan
    karlka1's Avatar
    karlka1 Posts: 2, Reputation: 1
    New Member
     
    #4

    Jul 5, 2010, 02:16 AM
    The problem you highlight would sound to be operation of the PRD - Pressure Relief Device, this is a safety valve fitted to your shower.

    Usual causes of operation is usually a blockage at the shower outlet - hose twisted / kinked or blocked shower head or perhaps a surge of pressure passing into the shower unit.

    To solve the problem you will need a new PRD which may be ordered directly from Triton Spares Dept(Tel : 0844 980 0750) and also check that there is no restriction to the outlet off the shower to ensure that the new PRD does not operate.

    Hope this info helps,

    Regards,
    TritonMan
    karlka1's Avatar
    karlka1 Posts: 2, Reputation: 1
    New Member
     
    #5

    Jul 5, 2010, 02:16 AM
    The problem you highlight would sound to be operation of the PRD - Pressure Relief Device, this is a safety valve fitted to your shower.

    Usual causes of operation is usually a blockage at the shower outlet - hose twisted / kinked or blocked shower head or perhaps a surge of pressure passing into the shower unit.

    To solve the problem you will need a new PRD which may be ordered directly from Triton Spares Dept(Tel : 0844 980 0750) and also check that there is no restriction to the outlet off the shower to ensure that the new PRD does not operate.

    Hope this info helps,

    Regards,
    TritonMan
    gizzmo2's Avatar
    gizzmo2 Posts: 1, Reputation: 1
    New Member
     
    #6

    Jan 7, 2011, 08:54 AM
    Shower keeps cutting out after a few minutes??
    massplumber2008's Avatar
    massplumber2008 Posts: 12,832, Reputation: 1212
    Senior Plumbing Expert
     
    #7

    Jan 7, 2011, 11:56 AM

    Sorry Gizzmo2...

    We don't get to work much with triton shower systems here, but maybe Tritonman will pop back and give you an idea on this so check back every now and then... never know.

    Good luck with this...

    Mark
    iandfleming's Avatar
    iandfleming Posts: 3, Reputation: 1
    New Member
     
    #8

    Mar 19, 2011, 02:24 AM
    Tritonman! - Having a new problem with my shower, I'm up here checking for solutions and saw my old posting from July 2010. YES it WAS the PRD valve. I replace it at very little cost... about a fiver I think. All good. Now I have heater element problems... but on way to solving.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search


Check out some similar questions!

Triton showers troubleshooting [ 1 Answers ]

I have a Triton T80 electric shower that is running at a very low rate of flow. I think the inlet filter needs cleaning but don't know how to get to it.

Triton troubleshooting [ 0 Answers ]

Triton combi hp thermostatic mixer shower.water lukewarm at hot setting and not very good pressure.tried changing shower head no difference.any ideas?

Triton T80I shower [ 3 Answers ]

My shower only let out cold water even when I put the temperature up, can some one help me

Harbor Breeze Triton #136954 HELP! [ 1 Answers ]

I installed a Harbor Breeze Triton #136954 ceiling fan without the receiver; hoping not to have to use the remote. PROBLEM Fan turns on & off from wall switch (works fine), lights do not. There is power to the bulb receptacles, so power isn't an issue. QUESTIONS Can I use the fan AND...


View more questions Search