    Lil_Sicilian's Avatar
    Lil_Sicilian Posts: 1, Reputation: 1
    New Member
     
    #1

    Mar 28, 2011, 07:17 AM
    t&p valve tu?
    My t&p valve leaks all the time. I have replaced it twice. The water pressure coming into my home is 100psi and the water temperature is approx 150 degrees. Any solutions
    massplumber2008's Avatar
    massplumber2008 Posts: 12,832, Reputation: 1212
    Senior Plumbing Expert
     
    #2

    Mar 28, 2011, 07:36 AM

    Hi Lilsicilian...

    Your water pressure is way to high. All plumbing codes require that any home that has pressure that exceeds 80 PSI needs to have a pressure regulating valve installed on the main cold water line into the home and the pressure choked down to about 60 PSI.

    Your temperature also exceeds requirements. Hot water is not supossed to exceed 120F so you need to set that down as well... ;)

    Let me know if you have more questions, OK?

    Mark
    Attached Images
     

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

B&S 14HP OHV intake valve/ worn cam lobe or tappet valve? [ 16 Answers ]

Hi, I've scoured the postings and found many people with similar problems but only 1 or 2 with identical problems to mine. I have a Toro Timecutter 14-38Z (model 74301 serial 230004085) zero turn mower with a Briggs %26 Stratton 14HP OHV engine (model 280H07-0166-E1) and it only has about 120 hours...

Hot water problem - faulty check valve or mixing valve? [ 8 Answers ]

Hi, We have a weird problem with hot water running cold in our apartment. At all of the faucets and taps we only get hot water for a minute or two and have to turn off the faucet/tap for 30 seconds and back on again to get hot water. Then the same thing happens again. To get continuous hot...

I'd like to install a ball valve on main water line will a "Viperlok" valve work? [ 1 Answers ]

I know sweat soldering a ball valve is best, but will a "push-ft" compression "Viperlok" brand ball valve work?---My pipes are old copper, and have a few minor scratches and pits---I also noticed a seam running down one side of pipe. This water line runs out into garden, but valve is in the house....

Cold water pressure relief valve leaking, not the TRP valve [ 5 Answers ]

Hello. Cold water pressure relief valve start to drip water through the drain pipe. I replaced it with a new one but it is also dripping water. I have reduced water pressure in the house to the minimum by turning main water supply valve but it still leaking. Thanks for your help.

Can I solder outlet side of a ball valve if the valve is closed and under pressure? [ 0 Answers ]

Can I solder outlet side of a ball valve if the valve is closed and under pressure?


View more questions Search