    jwalke11's Avatar
    jwalke11 Posts: 1, Reputation: 1
    New Member
     
    #1

    Dec 3, 2010, 02:14 PM
    My studor mini valve won't vent.
    I have a studor mini vent under my sink that will not let the water drain out - water drains when I remove the vent. I tried to replace it but got the same results. Is there a something you have to do to 'activate' a studor valve? I snaked the line underneath and it is clear. Any suggestions?
    ma0641's Avatar
    ma0641 Posts: 15,675, Reputation: 1012
    Uber Member
     
    #2

    Dec 3, 2010, 02:28 PM
    You don't have to activate a studor vent.. Remove the vent, clean the end and then try to suck air through it from the threaded end. If you get air, the vent is good. Can you post a diagram of the drain system, something doesn't sound right.
    massplumber2008's Avatar
    massplumber2008 Posts: 12,832, Reputation: 1212
    Senior Plumbing Expert
     
    #3

    Dec 3, 2010, 04:23 PM

    Hi guys...

    Yeah, you can try to clean the old studor vent or simply replace it... super cheap and super easy to do... :)

    That being said, I've seen similar circumstances as you suggest and the drain line was still clogged even after replacing the vent. Here, with the vent out all was fine (as is your drain), but when even a new vent was installed with the reduced air intake the drain didn't drain properly and the drain had to be snaked again, just a little farther out. My point is to not totally rule out resnaking the drain...could still be an issue.

    Cheapest bet would be to replace the studor vent and see if all is fixed. If all is not fixed, be prepared to snake the drain just a little further.

    Let us know the result, OK?

    Thank you...

    Mark
    ma0641's Avatar
    ma0641 Posts: 15,675, Reputation: 1012
    Uber Member
     
    #4

    Dec 3, 2010, 09:01 PM
    Comment on massplumber2008's post
    I wasn't suggesting cleaning it. I was suggesting cleaning the thread area of sealing compound and putting a negative pressure from the thread end. That will tell you if the valve is stuck
    massplumber2008's Avatar
    massplumber2008 Posts: 12,832, Reputation: 1212
    Senior Plumbing Expert
     
    #5

    Dec 4, 2010, 06:25 AM

    Jeez Brian, I was actually trying to "glaze" over the fact that you actually told someone to SUCK on an old, dirty studor vent, but since you brought it up I got to tell you, I sure as heck wouldn't put anything up to my mouth from an old drain line... don't care how much you cleaned it... still loaded with all kinds of bacteria and if sucked deep into the lungs could make someone sick... ;) Double yuck!

    To test the spring mechanism you should only need to push on the mechanism itself with a screwdriver or if totally enclosed you can grab it with a needlenose pliers...

    In my opinion, replacing the unit is still the best and CLEANEST approach here and then they can snake the drain again if needed.. as above.


    Mark
    speedball1's Avatar
    speedball1 Posts: 29,301, Reputation: 1939
    Eternal Plumber
     
    #6

    Dec 4, 2010, 06:41 AM
    After testing the AAV and finding it in working order I would began to suspect that back pressure is stopping the drain action. And what causes back pressure?
    A partial blockage in the horizontal line in the wall. Remove the trap and send the snake up into the wall, (see image) You will hit a bend about 8 inches in but once past that you'll only have 6 more feet to go. Good luck, Tom
    Attached Images
     

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Studor Mini-Vent [ 5 Answers ]

I recently had my kitchen remodeled and the plumber installed a Studor Mini-Vent under the sink. Due to space limitations, he installed it sideways and didn't glue the PVC pipes together so it's easily removed. Is this a proper installation? I am pretty sure this (either the vent or the break in...

Studor vent (air admittance vent) [ 3 Answers ]

I want to install a utility sink in my garage, which will require approx a 30 ft run of 11/2 " drain pipe. The 11/2" will be going into the 3" main drain line. I should be able to get 1/4" per foot pitch over the 30 ft run. My guestion is ,will I need to install a studor vent at the sink trap?

Studor vent vs. Vent pipe [ 8 Answers ]

Applications for each? Differences? Pros/Cons?

Do I need a Studor Vent [ 11 Answers ]

The contractor who is remodeling my kitchen installed a new sink. The drain pipe goes under the floor through the crawl space. He said there is enough height to the drainage, so there is no need to install a vent. I have read that you need to install a studor vent if it's hard to connect to the...

Using "Studor" mini vent in bathroom wall [ 1 Answers ]

I am completely renovating a bathroom in a 1973 mobile home. There is no vent stack from any of the toilet, tub or lav fixtures. I plan to install the "Studor" vent in the wall. Can I use one vent for two fixtures or does each fixture need it's own vent?


View more questions Search