    Shower won't fire boiler
    I have a Worcester 35 CDi boiler. Recently the shower in the ensuite and the shower in the bathroom won't fire the boiler when turned on. If the heating is on, the showers work but not on their own. The hot water in each sink and the bath works and if you take the head of the showers, the water coming out of the end of the hose is hot and the boiler fires. Its tempting to think it's the shower head that's bunged up. They have have been cleaned thoroughly and the force of the water coming out is high. If it was the shower head, why would it work if the heating was on?

    Any ideas would be great.

    Heather
    doug238's Avatar
    doug238 Posts: 1,560, Reputation: 62
    Ultra Member
     
    #2

    May 6, 2008, 06:29 PM
    Sounds like the boiler is activated by a flow switch. Even though the shower head appears to be strong, it may not have the required gpm [gallon per minute] flow to activate the flow switch. There is likely a flow restricter in the shower head.
    speedball1's Avatar
    speedball1 Posts: 29,301, Reputation: 1939
    Eternal Plumber
     
    #3

    May 8, 2008, 07:46 AM
    Quote Originally Posted by heathersc
    I have a Worcester 35 CDi boiler. Recently the shower in the ensuite and the shower in the bathroom wont fire the boiler when turned on. If the heating is on, the showers work but not on their own. The hot water in each sink and the bath works and if you take the head of the showers, the water coming out of the end of the hose is hot and the boiler fires. Its tempting to think its the shower head thats bunged up. They have have been cleaned thoroughly and the force of the water coming out is high. If it was the shower head, why would it work if the heating was on?

    Any ideas would be great.

    Heather
    Hi Heather,
    There's a water saver in your shower head that looks like a rubber washer with holes around the sdge. Pry it out and toss it. Work better now? Regards, Tom

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Weil-mclain boiler cg series won't fire up [ 2 Answers ]

Pilot stays on zones open up after thermostat calls for heat but boiler don't fire up what could it be. Any ideas? Txs.

How long should a boiler fire [ 4 Answers ]

We have a group home with a 8+ year old Lochinvar 300,000 BTU LP gas outdoor furnace. I suspect that the installer just shot from the hip on size (retrofit for ceiling electric). It is supplying 4 zones 60 to 100 feet away in the attic with 18"x24" heat exchangers (if memory serves). These are...

Boiler won't fire up [ 1 Answers ]

I have a very old boiler that heats the home with the water in cast iron pipes in the floor - concrete slab. I recently added a second floor with a forced air furnace. I started up the new furnace and now the boiler won't fire. Pilot light is still on. I turned off the furnace and the gas line...

95 civic won't fire [ 1 Answers ]

My 95 civic won't start I'm getting fuel, spark, but it just keeps turning over but doesn't fire. It crunk up and ran for a little bit the other day and thought I had it fixed but went out the othe rday and it doesn't do any thing but just turn over any suggestions

Main gas won't fire [ 1 Answers ]

Heil 7000 High Eff Purge blower turns on Pilot fires, main gas will not open / fire or rather honeywell (VR82041075) MV won't open. Electronic board MV output voltage is what to valve? No manual. Module HQ1005962EX


View more questions Search