    Problems With T&P valve releasing on hot water heater
    I have a 40 gallon hotpoint gas hot water heater in a foreclosure I bought that set for about a year empty. I had hot water pouring out a line under the house so I capped it (stupid I know). Well after talking to a home inspector he told me that it was probably my pressure relief line and my t and p valve was probably bad so I replaced it and yet still hot water is shooting out the line when I turn my water on. For a few hours the water lines in my house just shook really bad and then the valve opened up. I have no idea what to do now. Do I need to buy a new hot water heater or is something else going on?
    hkstroud's Avatar
    hkstroud Posts: 11,929, Reputation: 899
    Home Improvement & Construction Expert
     
    #2

    Sep 20, 2011, 03:02 AM
    I must not be understanding. Sounds like you are saying that you had a leaking water line and some one told you it might be your T&P valve and you replace it.
    Where was the leak? Where is the water heater. T&P's usually empty into or close to a floor drain.

    Did you fill the water heater before turning it on? Sound like you did not and the little bit of water in turned to steam before the thermostat shut it off.

    When filling a water heater you have to open a hot water valve to let the air in the tank out before lighting.
    speedball1's Avatar
    speedball1 Posts: 29,301, Reputation: 1939
    Eternal Plumber
     
    #3

    Sep 20, 2011, 06:13 AM
    T & P valves open up for two reasons so what's the PSI entering your house and what temperature setting on your thermostat? AS far as the pipes shaking and making noise as you fired up the heater that's explained by poor maintenance .
    If you do not flush,(not drain) your heater on a regular basis it will build up mineral on the bottom of the tank. When the flame comes on it turns the water trapped under the mineral to steam and the steam escaping is what you hear. Let me show you how to flush your heater. Attach a hose to the boiler drain at the bottom of the tank. With the pressure on, open the boiler drain and let it run until the water runs clear. You will see a spurt of red,(rust) and some white grains,(lime or calcium carbonate). The whole thing shouldn't take more then a few minutes. Don't forget to flush it out every month. Your heater will thank you for it. You might want to consider cleaning the screens on your aerators if you have a high mineral buildup. If the problem still persists after you have flushed, you will have to drain the heater, remove the boiler drain and go up in the bottom of the tank with a wood or plastic rod, (not metal) and try to break up the mineral and flush it out. Check the house pressure and temperature setting. Let me know what you find. Good luck tom
    ma0641's Avatar
    ma0641 Posts: 15,675, Reputation: 1012
    Uber Member
     
    #4

    Sep 20, 2011, 11:48 AM
    I believe there are 2 issues, high house pressure and sediment in the tank. If you replaced the TPV, you should also check the regulated water pressure. Get a teast gauge and connect it to a REGULATED hose bib or on the HW heater, pressure should be in the 50#range. If much higher, find the house pressure regulator and with a faucet open, slowly turn the top stem to the left, loosening it. Note if the water pressure drops. If not, you should probably consider changing the regulator. It may or may not be a DIY job since some are pipe threaded and fairly easy to change while others are sweated in. The HW rumbling is possibly caused bu a layer of sediment and the heated water actually bubbles through the sediment. Note other posts have given you directions to power flush the heater.

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Water Heater problems, no water flow after pressure valve change [ 4 Answers ]

I changed my pressure release valve, now I can not hot water flw in my house.

Water heater pressure relief valve is releasing water [ 3 Answers ]

It appears my pressure relief valve is leaking as the water is dripping from the pipe outside. There are no other water heater issues. It's a dual valve system. The 125psi is leaking to outside, the 125psi is perfectly dry. People I've called in want to replace the entire water heater which...

Hot water heater valve [ 3 Answers ]

:confused: What do you think is wrong with a relief valve that does not leak when the electric is turned off, but leaks when the electric is turned back on and mild(100 degrees or so) hot water comes from the faucets.:confused:

Hot water pressure valve releasing [ 5 Answers ]

My pressure relief valve on the hot water heater is releasing every couple of days. My tank is in an overflow pan. I get about an inch of water in the pan each time. We've replaced the hot water heater. Before that, we replaced the pressure relief valve (twice) on the old water heater. Problem...


View more questions Search