    augster's Avatar
    augster Posts: 1, Reputation: 1
    New Member
     
    #1

    Jun 16, 2007, 08:32 AM
    Power Vent Rheem Hot Water Heater
    I have a Rheem Power Vent hot water heater, model 21VP40-1. My problem is that it will not stay lit on the final start up stage. It operates OK, stays lit, if turned on manualy on the unit. I have replaced the gas valve. I am leaning toward the control module. Any advice?
    speedball1's Avatar
    speedball1 Posts: 29,301, Reputation: 1939
    Eternal Plumber
     
    #2

    Jun 17, 2007, 01:08 PM
    : Look out near the gas meter. You should see a inverted tee, (tee turned upside down)with a pipe pointing down. This is a drip loop installed to collect moisture so that it won't get in your gas line. Over time this drip loop will fill up and needs to be drained. If it's not drained water will enter with the gas and put out the pilot light. Some drip loops have a petcock at the bottom so you can drain it. Others have a hard cap that must be remover with a wrench. Shut off the gas at the meter, open up the drip loop and drain it. If it has a hard cap, don't forget to wrap the threads with teflon tape before you put it back. When you turn the gas back on paint the threads with liquid soap and check for leaks,(bubbles). Hope this helps and thank you for rating my reply. TOM
    Answer : Let me paste up a article I found on the web that you may find of interest.
    Troubleshooting Gas Water Heaters
    Knowing how to light the pilot is one key to living with a gas water heater; see the instructions on the tank. For safety, a gas heater has a thermocouple. This is thermoelectric device that impinges on the pilot flame and shuts off the gas if the pilot light goes out. The gas flame should be blue. If it's orange, adjust the shutter; if it's still orange, call for service.
    Twice a year, inspect the flue assembly to be sure it's properly aligned and all its joints are sealed. Then check the flue by placing your hand near the draft diverter (with the burner on); air flowing out indicates an obstruction that should be removed. Every year or two, shut off the gas, remove the access panel, and clean the burner ports, using stiff wire or a needle. If you ever smell gas, get out of the house immediately and call the gas company.
    There is no hot water.<<
    Check for:
    Unlit pilot light.
    Pilot light won't keep burning.<<
    Clogged burner
    Defective thermocouple.
    The gas is not coming out.<<
    Remedies:
    Carefully relight the pilot.
    Make sure the gas controls are completely turned on. Then check the thermocouple and be sure it is firmly connected to the gas control unit and positioned near the pilot flame.
    Call a qualified contractor.
    Replace the thermocouple.
    Call the Gas Company.
    There isn't enough hot water.<<
    Check for:
    Incorrectly set thermostat.
    Defective thermostat.
    Exposed hot water pipes
    Too small of a water tank
    Clogged burner.
    Sediment has formed in the tank.
    Leaking hot water faucets.
    Remedies:
    Turn the thermostat higher.
    Call a qualified contractor.
    Insulate the hot water pipes.
    Install a larger water tank.
    Call a qualified contractor.
    Turn off the gas and drain the tank.
    Repair or replace the faucets.
    The water heater is very noisy.<<
    Check for:
    Scale and sediments in the tank.
    Remedy:
    Turn off the gas and flush the tank.
    The water is too hot.<<
    Check for:
    Wrong setting on thermostat.
    Defective thermostat.
    Blocked exhaust vent.
    Remedies:
    Reset the thermostat.
    Call a qualified contractor.
    Check the vent and clear it.
    Water is leaking from the heater.<<
    Check for:
    Leak in the draincock.
    Leaking safety valve.
    Hole in the tank.
    Leak in the plumbing connection.
    Remedies:
    Close it tightly or replace it.
    Check the water temperature. If it's too hot, the thermostat may be broken. If the safety valve is defective, replace it.
    Buy a new water heater.
    Call a plumber. <<< Before you call a plumber flush,(not drain) your heater. Good luck, TOM
    patngin's Avatar
    patngin Posts: 1, Reputation: 1
    New Member
     
    #3

    Jun 25, 2008, 08:55 PM
    I have the same tank and had the same problem. Repairman was going to do $300 worth of stuff and I checked at another place. They told me to remove the shroud on the power vent and clean the fan using a small sof paintbrush and vacuum and put it back together. Presto it worked. He was going to replace the pressure switch and control module. No need. If it is dirty it causes the pressure not to be right to the little hose that runs to tank. Also make sure the hose is not clogged.

    Pat

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

No hot water - hot water heater and cold working [ 1 Answers ]

HELP! Its freezing out and we have NO hot water! Cold is working fine everywhere - but nothing comes out of the hot side anywhere. The hot water heater appears to be working? Did the hot water pipes freeze? Why the hot side and not the cold? Please help.

Hot Water Heater not keeping water hot [ 1 Answers ]

Hi I am having trouble with my hot water heater. I believe it's a gas water heater. I have a problem with my water not staying hot. I have no problem getting hot water in the morning if I've run the dishwasher or the washer the night before. However If I haven't used much water recently, the...

Non Power Direct Vent Hot Water Tank [ 4 Answers ]

Hello, I am building a garage and plan on putting in a hot water tank. Since it's a garage I wanted to get the direct vent type to get the air from outisde the garage. Question is, Can I use a non powered direct vent hot water tank with vinyl siding on the outside of my garage? I didn't want...

Water Heater Vent Fan runs constantly [ 1 Answers ]

I have a 75 Gallon Natural Gas State Select Water Heater. Model # PR675NRVTZ. It has a fan on top that vents the gas to the outside. Normally, this fan only runs when the water is being heated. Now, the fan runs constantly eben when the water is not being heated. I do not have the wiring diagram,...


View more questions Search