    Off the mark by a quarter of an inch with toilet install
    I am installing a sterling dual flush toilet which is to be installed as close to the finished wall as possible. When measuring my center line to the drain I am at 11 3/4" instead of 12" are there any ideas out there besides an offset toilet flange? I can't find a 1/2 to 1" offset closet flange do you all know of one? Will I be okay with the 1/4" off ?
    It is a basement bathroom that won't be used much and there is no longer access to the drain line . Thanks for all your help.

    Nina
    truck 41's Avatar
    truck 41 Posts: 221, Reputation: 21
    Full Member
     
    #2

    Jun 8, 2008, 03:53 PM
    Hello Nina, if you have 11 3/4" from the finish wall then you should be in good shape, you should still have a small gap between the wall and the back of the toilet about 1/4" . In most cases if you needed that 1/4" you should be able to slide toilet foreword that much , but I don't think that will be necessary. Put your closetbolts on the flange and set your toilet in place without the wax ring, and set the tank in place so you can see that the tank is going to set right on the bowl. If your happy with the fit, then take off the tank and toilet, and set the wax ring in place, set your toilet and complete assembly. You should be all right. Goodluck-------Zeke
    massplumber2008's Avatar
    massplumber2008 Posts: 12,832, Reputation: 1212
    Senior Plumbing Expert
     
    #3

    Jun 8, 2008, 05:44 PM
    Hey Nina:

    In fact, you are better off with 11.75" rough in from finish wall then with a true 12" rough in.

    Set the bowl like Zeke suggested... whatever space you end up with between finish wall and toilet tank is closer than if you had a true 12" rough... ;)

    You will definitely not be too close!! In fact, most 12" rough toilets today are closer to an 11" rough... so you should still expect a gap (between wall and tank) of about an 1/4 to 1 inch!

    Let us know how it goes and let us know the distance between tank and finished wall when all done... be sure to level the tank from front to back and left to right... without cracking tank!

    MARK

    .
    foursquare's Avatar
    foursquare Posts: 3, Reputation: 1
    New Member
     
    #4

    Jun 9, 2008, 06:27 AM
    Another question I called sterling and they said I am too close that there is an 1/8" tolerance. Do you all think think that I will be okay anyway? Or am I looking at an offset flange? Thanks again, Nina
    massplumber2008's Avatar
    massplumber2008 Posts: 12,832, Reputation: 1212
    Senior Plumbing Expert
     
    #5

    Jun 9, 2008, 06:39 AM
    NINA... you should be all set here! As long as you are 11.75 inches from the finish wall to the center of the toilet flange and no less!

    I install kohler toilets all the time... and they never end up as tight to the wall as the specification sheets suggest.

    If it makes you feel better... Dry fit the toilet and tank WITHOUT WAX GASKET in place.

    I am quite confident that this will fit just right for you!
    iamgrowler's Avatar
    iamgrowler Posts: 1,421, Reputation: 110
    Ultra Member
     
    #6

    Jun 9, 2008, 06:43 AM
    Quote Originally Posted by foursquare
    Another question I called sterling and they said I am too close that there is an 1/8" tolerance. Do you all think think that I wil be okay anyway? or am I looking at an offset flange? thanks again, Nina
    I think you'll be fine -- If it's the Sterling Dual Flush I think it is, a bit of advice on setting the plastic floor flange, though.

    If this is the one with the white or gray plastic adapter that bolts to the closet flange and then the stool slides back into a black rubber boot, then buy an oversized stainless steel hose clamp and clamp the back of the rubber boot to the adapter body.

    Also -- Depending on your floor finish, you might want to set the stool on a new and clean piece of cardboard before sliding it back into the boot, some of these stools are badly cast and will leave scratch marks on wood, linoleum or soft stone floors.
    speedball1's Avatar
    speedball1 Posts: 29,301, Reputation: 1939
    Eternal Plumber
     
    #7

    Jun 9, 2008, 06:47 AM
    Quote Originally Posted by foursquare
    Another question I called sterling and they said I am too close that there is an 1/8" tolerance. Do you all think think that I wil be okay anyway?Will I be okay with the 1/4" off or am I looking at an offset flange? thanks again, Nina
    You're going to be just fine Nina. As both Mark and Zeke pointed out you have some "wiggle room" at the flange.
    Here's a little tip. When tightening the tank bolts do not tighten them all the way down. Leave a little play in the tank so if someone leans back it won't crack the china case of the tank where the tank bolts go through. Good luck, Tom
    foursquare's Avatar
    foursquare Posts: 3, Reputation: 1
    New Member
     
    #8

    Jun 13, 2008, 12:55 PM
    I tested the fit of the toilet and it will just work. It is sitting against the tile on the wall. The toilet does not attach via flange bolts but with included hardware. If any of you do need to set the kohler persuade or the sterling stockton toilet, their strict 12" rough in should be adhered to. Thanks to everyone that answered my question I appreciate the advice.

    Nina

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Adhesive? New ceramic tile install - one inch hex shape sheets [ 5 Answers ]

Hello I am putting in a brand new full bath where there had been just a half bath.. I am done the roughing in and the framing, cementboard, sheetrock, etc. - and I have a question about the tile installation. For the floor, I chose an older style of tile that is the white octagon/hexagon...

Install 3 inch toilet drain in concrete slab [ 1 Answers ]

I want to add a new toilet to the laundry room in our garage which is located on a concrete slab. The plumbing is already installed for a laundry sink and a washer. This will require adding a 3 inch pvc drain for a toilet that will have to be installed through the concrete slab which will be inches...

5 inch wide pine flooring install and moisture content [ 2 Answers ]

Hello I bought 600 square feet of 5 inch wide pine flooring for my third floor - guest room and small office space. The rooms are currently old tongue & groove over joists subflooring with no finished floor ever installed since 1920. I was going to install the new pine running perpendicular to...

Moving a toilet over an inch. [ 6 Answers ]

I have to move my toilet over an inch away from the wall per inspector's order. The top of the main sewer line is 4" below ground level encased in the concrete foundation with a 4" 90 degree street ell (spg x hub) at the end. The end of the elbow is .5" below ground level. I found an abs offset...

Moving a toilet over an inch above an already finished floor [ 1 Answers ]

I am replacing a toilet in my mother in laws house. Her original sewage pipe is cast iron set in a concrete foundtion. I have to move the toilet about 1and a half inches and I need to know how to do this. I was told that there was a way but I need to know how to do it.


View more questions Search