    How can I locate my studor vent without too much destruction?
    I have a swere smell in my bathroom that is in a finished basement. The basement was finished by the builder and not done after purchase. There is a studor vent somewhere in the bathroom that is not working so we want to find it and replace it. Where should I start cutting to look. The wall, the ceiling or is there another non-invasive way to find this vent.
    speedball1's Avatar
    speedball1 Posts: 29,301, Reputation: 1939
    Eternal Plumber
     
    #2

    Sep 11, 2012, 09:22 AM
    It's always too bad when builders don't follow code. It's against code to wall in a AAV where it can't be replaced or serviced. I would call the builder and ask, If I had to guess AND the bath room group was wet vented I'd open up the wall over the vanity. Good luck, Tom
    ma0641's Avatar
    ma0641 Posts: 15,675, Reputation: 1012
    Uber Member
     
    #3

    Sep 11, 2012, 12:45 PM
    How do you know there is an AAV? Could be a bad wax ring on the toilet.
    phoebeisawsome's Avatar
    phoebeisawsome Posts: 15, Reputation: 0
    New Member
     
    #4

    Sep 11, 2012, 12:48 PM
    I think you should start with the top and bottom of the corners on the walls and then start on the floor corners then the celing it happened with my friend
    ma0641's Avatar
    ma0641 Posts: 15,675, Reputation: 1012
    Uber Member
     
    #5

    Sep 11, 2012, 12:54 PM
    Quote Originally Posted by phoebeisawsome View Post
    i think you should start with the top and bottom of the corners on the walls and then start on the floor corners then the celing it happened with my friend
    ?? To what are you referring? A studer vent? Never saw one on a floor level!
    phoebeisawsome's Avatar
    phoebeisawsome Posts: 15, Reputation: 0
    New Member
     
    #6

    Sep 11, 2012, 12:56 PM
    Well my friend had one there but check on the walls and celings
    massplumber2008's Avatar
    massplumber2008 Posts: 12,832, Reputation: 1212
    Senior Plumbing Expert
     
    #7

    Sep 11, 2012, 03:22 PM
    Hi Jones

    Tom is correct in stating that the place to start looking is right inside or just above the vanity (behind the mirror or medicine cabinet). Here, if a bathroom group has been WET VENTED the lavatory vent will almost always get the studor vent so it is going to be the best place to start.

    Brian also presents a good suggestion in that a bad wax gasket could cause odor issues although this will usually result in staining/mositure at the base of the toilet but it certainly could be worth exploring!

    Look inside the vanity.. up high. If the AAV isn't there then as Tom presented, look behind the mirror or medicine cabinet.. most likely the vent will be found there.

    Good luck!

    Mark

Not your question? Ask your question View similar questions

 

Question Tools Search this Question
Search this Question:

Advanced Search

Add your answer here.


Check out some similar questions!

Studor vent (air admittance vent) [ 3 Answers ]

I want to install a utility sink in my garage, which will require approx a 30 ft run of 11/2 " drain pipe. The 11/2" will be going into the 3" main drain line. I should be able to get 1/4" per foot pitch over the 30 ft run. My guestion is ,will I need to install a studor vent at the sink trap?

Studor vent vs. Vent pipe [ 8 Answers ]

Applications for each? Differences? Pros/Cons?

Studor vent [ 8 Answers ]

I have been reading the problem that one man had with the vent? I am confused. If you remove the vent and the water goes out with no problem and does not back up even through the open pipe why would the drain be clogged? I have the problem with the vent on the water backs up in both sinks. ...

Studor vent [ 3 Answers ]

How good to these things work? And what are the skematics for this thing?

Do I need a Studor Vent [ 11 Answers ]

The contractor who is remodeling my kitchen installed a new sink. The drain pipe goes under the floor through the crawl space. He said there is enough height to the drainage, so there is no need to install a vent. I have read that you need to install a studor vent if it's hard to connect to the...


View more questions Search